Inefficiency of upward displacement operating theatre ventilation

被引:38
作者
Friberg, B
Friberg, S
Burman, LG
Lundholm, R
Ostensson, R
机构
[1] NO UNIV HOSP,DEPT ORTHOPAED,UMEA,SWEDEN
[2] NO UNIV HOSP,DEPT CLIN MICROBIOL,UMEA,SWEDEN
[3] SWEDISH INST INFECT DIS CONTROL,S-10521 STOCKHOLM,SWEDEN
关键词
operating rooms; ventilation; clothing; particle counts; colony counts; microbiology;
D O I
10.1016/S0195-6701(96)90012-2
中图分类号
R1 [预防医学、卫生学];
学科分类号
1004 ; 120402 ;
摘要
A new thermally based ventilation system ('Floormaster') with inlet of cool clean air at floor level, and evacuation at the ceiling of the air warmed by activity in the room (upward displacement ventilation, 17 air changes/h) was compared with a standard positive pressure (plenum) ventilation system with air supply through an inclined perforated screen along one wall at the ceiling and evacuation at floor level (conventional turbulent or mixing system, 16 air changes/h). The study was made during rigidly standardized sham operations (N = 20) performed in the same operating room by a six-member team wearing non-woven disposable or cotton clothing. In general the upward displacement system removed dust particles too small to carry bacteria (0.16- < 0.3 mu m, 0.001 < P < 0.01) more efficiently than the conventional system. However, the displacement system also yielded two to threefold higher air and surface bacterial counts in areas important for surgical asepsis (Round area, instrument table) especially with regard to bacterial sedimentation (0.001 < P < 0.05). The major shortcoming of the displacement system was insufficient elimination of the larger bacteria-carrying particles. The type of clothing worn by the members of the team did not influence the overall results. We conclude that an upward displacement system will lead to increased counts of airborne and sedimenting bacteria and thus increase the risk of postoperative infection in comparison with conventional operating room ventilation systems.
引用
收藏
页码:263 / 272
页数:10
相关论文
共 15 条
[2]   VENTILATION CONDITIONS AND AIR-BORNE BACTERIA AND PARTICLES IN OPERATING-THEATERS - PROPOSED SAFE ECONOMIES [J].
CLARK, RP ;
REED, PJ ;
SEAL, DV ;
STEPHENSON, ML .
JOURNAL OF HYGIENE, 1985, 95 (02) :325-335
[3]  
CRUSE PJE, 1980, SURG CLIN N AM, V60, P27
[4]  
GERHARDT E, 1987, VVS, V23, P8
[5]   AEROBIOLOGY IN THE OPERATING-ROOM - A REVIEW [J].
HAMBRAEUS, A .
JOURNAL OF HOSPITAL INFECTION, 1988, 11 :68-76
[6]  
HILLERBRANT B, 1990, SWISS CONTAMINATION, V3, P336
[7]   INFECTION CONTROL AND THE DESIGN OF A NEW OPERATING-THEATER SUITE [J].
HUMPHREYS, H .
JOURNAL OF HOSPITAL INFECTION, 1993, 23 (01) :61-70
[8]   AIR BACTERIAL AND PARTICLE COUNTS IN TOTAL HIP-REPLACEMENT OPERATIONS USING NON-WOVEN AND COTTON GOWNS AND DRAPES [J].
JALOVAARA, P ;
PURANEN, J .
JOURNAL OF HOSPITAL INFECTION, 1989, 14 (04) :333-338
[10]   DIMENSIONS OF SKIN FRAGMENTS DISPERSED INTO AIR DURING ACTIVITY [J].
MACKINTOSH, CA ;
LIDWELL, OM ;
TOWERS, AG ;
MARPLES, RR .
JOURNAL OF HYGIENE, 1978, 81 (03) :471-&