Experimental-Numerical Comparison for a High-Density Data Center: Hot Spot Heat Fluxes in Excess of 500 W/ft 2

被引:22
作者
Shrivastava, Saurabh K. [1 ]
Iyengar, Madhusudan [2 ]
Sammakia, Bahgat G. [3 ]
Schmidt, Roger [2 ]
VanGilder, James W. [1 ]
机构
[1] Amer Power Convers Corp, Billerica, MA 01862 USA
[2] IBM Syst & Technol Grp, Poughkeepsie, NY 12601 USA
[3] SUNY Binghamton, Dept Mech Engn, Binghamton, NY 13902 USA
来源
IEEE TRANSACTIONS ON COMPONENTS AND PACKAGING TECHNOLOGIES | 2009年 / 32卷 / 01期
关键词
Cooling; data center; experimental measurement; numerical validation; raised floor;
D O I
10.1109/TCAPT.2008.2011558
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper uses previously published experimental data to present a comparison between test results and numerical simulations. The example considered is a large 7400 ft(2) data canter that houses over 130 heat-producing racks (1.2 MW) and 12 air conditioning units. Localized hot spot heat fluxes were measured to be as high as 512 W/ft(2) (5.5 kW/m(2)) for a 400 ft2 (37 m(2)) region. A numerical model based on Computational Fluid Dynamics (CFD) was constructed using inputs from the measurements. The rack inlet air temperature was considered to be the basis for experimental versus numerical comparison. The overall mean rack inlet temperature predicted numerically at a height of 1.75 m is within 4 degrees C of the test data with a rack-by-rack standard deviation of 3.3 degrees C.
引用
收藏
页码:166 / 172
页数:7
相关论文
共 10 条
[1]  
*ASHRAE, 2005, ASHRAE PUBL
[2]  
Devore J.L., 2000, PROBABILITY STAT ENG
[3]  
*FLOM SURR, FLOVENT V5 1 SOFTW
[4]  
MADARA S, 2004, DATA CTR MANAGEM NOV
[5]  
Montgomery D.C., 2001, DESIGN ANAL EXPT, V5th, P392
[6]  
PATEL C, 2001, P INT EL PACK TECHN, P821
[7]  
Schmidt R., 2004, Proceedings of the ASHRAE Nashville Conference, P604
[8]  
SCHMIDT RR, 2005, P ASHRAE ANN M S DEN
[9]   Comparative analysis of different data center airflow management configurations [J].
Shrivastava, Saurabh ;
Schmidt, Roger ;
Sammakia, Bahgat ;
Iyengar, Madhusudan .
Advances in Electronic Packaging 2005, Pts A-C, 2005, :329-336
[10]   Airflow uniformity through perforated tiles in a raised-floor data center [J].
VanGilder, James W. ;
Schmidt, Roger R. .
Advances in Electronic Packaging 2005, Pts A-C, 2005, :493-501