Study on a Series Resistive SFCL to Improve Power System Transient Stability: Modeling, Simulation, and Experimental Verification

被引:93
作者
Sung, Byung Chul [1 ]
Park, Dong Keun [1 ]
Park, Jung-Wook [1 ]
Ko, Tae Kuk [1 ]
机构
[1] Yonsei Univ, Sch Elect & Elect Engn, Seoul 120749, South Korea
关键词
Damping performance; equal-area criterion; fault protection; superconducting fault-current limiter (SFCL); transient stability; transmission system; FAULT CURRENT LIMITER; ENHANCEMENT; OPERATION;
D O I
10.1109/TIE.2009.2018432
中图分类号
TP [自动化技术、计算机技术];
学科分类号
080201 [机械制造及其自动化];
摘要
This paper presents a study to determine the optimal resistive value of a superconducting fault-current limiter (SFCL) for enhancing the transient stability of a power system more effectively. A resistive type of SFCL, which provides quick system protection, is modeled. Then, the optimal resistive value of the SFCL connected in series with a transmission line during a short-circuit fault is systematically determined by applying the equal-area criterion based on the power-angle curves. To verify the effectiveness of the optimal value of the proposed SFCL for reducing the value of fault current, several case studies are carried out by both simulation and experimental tests, particularly including the 220-V/300-A-scale laboratory and 13.2-kV/630-A-scale distribution system hardware tests. The results show that the optimal resistive value of the SFCL determined by the proposed method improves effectively the transient stability and damping performances during a fault over the other values determined by an ad hoc approach.
引用
收藏
页码:2412 / 2419
页数:8
相关论文
共 18 条
[1]
[Anonymous], 1999, SPRINGER SCI
[2]
Renewable energy systems with photovoltaic power generators: Operation and modeling [J].
Bialasiewicz, Jan T. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2008, 55 (07) :2752-2758
[3]
Goto Y, 2000, 2000 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY, VOLS I-III, PROCEEDINGS, P275, DOI 10.1109/ICPST.2000.900069
[4]
Experimental study on limiting operation of superconducting fault current limiter in double circuit transmission line model system [J].
Hatta, H ;
Muroya, S ;
Nitta, T ;
Shirai, Y ;
Taguchi, M .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2002, 12 (01) :812-815
[5]
Kundur P., 1994, POWER SYSTEM STABILI
[6]
MUMFORD F, 1995, IEE C FAULT CURR LIM
[7]
High-temperature superconductor fault current limiters: concepts, applications, and development status [J].
Noe, Mathias ;
Steurer, Michael .
SUPERCONDUCTOR SCIENCE & TECHNOLOGY, 2007, 20 (03) :R15-R29
[8]
Single DC reactor type fault current limiter for 6.6 kV power system [J].
Nomura, T ;
Yamaguchi, M ;
Fukui, S ;
Yokoyama, K ;
Satoh, T ;
Usui, K .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2001, 11 (01) :2090-2093
[9]
Reliability issues in photovoltaic power processing systems [J].
Petrone, Giovanni ;
Spagnuolo, Giovanni ;
Teodorescu, Remus ;
Veerachary, Mummadi ;
Vitelli, Massimo .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2008, 55 (07) :2569-2580
[10]
Saadat H., 2004, POWER SYSTEM ANAL