Modelization of current sensors by finite elements method

被引:20
作者
Letosa, J [1 ]
Artal, JS [1 ]
Samplón, M [1 ]
Usón, A [1 ]
Arcega, FJ [1 ]
机构
[1] Univ Zaragoza, Escuela Univ Ingn Tecn Ind, Dept Elect Engn, Zaragoza 50018, Spain
关键词
high current; current sensor; modelization; calibration; finite elements method; N-turn coils;
D O I
10.1016/j.measurement.2003.11.005
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Accurate high current measurements require the use of devices which are difficult to calibrate since neither it is easy to obtain the current needed nor to set up a proper testing rig in the laboratory. Nevertheless, a straight wire carrying a high current can be replaced by an N-turn coil fed with an N-times lower current. In this paper, the uncertainty associated with the use of N-turn coils in calibration of clamp-type current meters has been estimated using the finite element method (FEM). The wire carrying the current to be measured is often incorrectly located with respect to the sensor. Hence, the effects of excentricity or rotation of the sensor with respect to the straight wire are also analysed by FEM and measured at 50 Hz in our metrology laboratory accredited by European Cooperation for Accreditation (EA). (C) 2003 Elsevier Ltd. All rights reserved.
引用
收藏
页码:233 / 241
页数:9
相关论文
共 5 条
  • [1] *EUR ACCR, 1997, PUBL REF EUR ACCR
  • [2] *ISO IEO OIML BIPM, 1992, GUID EXPR UNC MEAS
  • [3] *MICR INC, EL MAT CAT
  • [4] Press W. H., 1997, NUMERICAL RECIPES C
  • [5] Silvester PP., 1996, FINITE ELEMENTS ELEC