Simplified numerical models for complex air supply diffusers

被引:80
作者
Srebric, J [1 ]
Chen, QY
机构
[1] Penn State Univ, Dept Architectural Engn, University Pk, PA 16802 USA
[2] MIT, Cambridge, MA 02139 USA
来源
HVAC&R RESEARCH | 2002年 / 8卷 / 03期
关键词
D O I
10.1080/10789669.2002.10391442
中图分类号
O414.1 [热力学];
学科分类号
摘要
Correct description of the flow and thermal information for an air supply diffuser is important for reliably predicting room air distribution by using computational fluid dynamics. Simplified methods that can be used to describe flow and thermal information from eight commonly used diffusers were developed in this study. The investigation used the box and momentum methods. The corresponding experimental data on airflow and temperature distributions from an environmental chamber have been used to validate the numerical methods. The box method with an appropriate box size is satisfactory for most of the diffusers. The momentum method performs well for five diffusers. Because the momentum method is simpler than the box method, the momentum method should be used whenever it is applicable.
引用
收藏
页码:277 / 294
页数:18
相关论文
共 28 条
[1]  
*CHAM LTD, 1998, PHENICS VERS 3 1
[2]   COMPARISON OF DIFFERENT K-EPSILON MODELS FOR INDOOR AIR-FLOW COMPUTATIONS [J].
CHEN, Q .
NUMERICAL HEAT TRANSFER PART B-FUNDAMENTALS, 1995, 28 (03) :353-369
[3]  
Chen Q, 1996, P ROOMVENT 96, V1, P227
[4]  
CHEN Q, 2000, RP1009 ASHRAE MIT
[5]  
Cheng-Tie Chen, 1991, Journal of Visual Communication and Image Representation, V2, P1, DOI 10.1016/1047-3203(91)90031-A
[6]  
EMVIN P, 1996, P ROOMVENT 96, V1, P219
[7]   CFD MODELING OF THE AIR AND CONTAMINANT DISTRIBUTION IN ROOMS [J].
FAN, YC .
ENERGY AND BUILDINGS, 1995, 23 (01) :33-39
[8]  
HEIKKINEN J, 1991, P 12 AIVC C AIR MOV, V3, P213
[9]  
HEIKKINEN J, 1994, P ROOMVENT 94, V1, P329
[10]  
Huo Y., 1996, P ROOMVENT 96, V2, P233