Unsteady thermal performance analysis of a room with serial and parallel duct radiant floor heating system using hot airflow

被引:48
作者
Bozkir, O
Canbazoglu, S [1 ]
机构
[1] Inonu Univ, Fac Engn, Dept Mech Engn, TR-44280 Malatya, Turkey
[2] Inonu Univ, Malatya Vocat Sch, Dept Tech Programs, TR-44080 Malatya, Turkey
关键词
radiant floor heating system; unsteady thermal performance;
D O I
10.1016/j.enbuild.2004.01.039
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In this study, the unsteady thermal performance of a test room heated by circulating hot airflow under the floor was analyzed with a developed mathematical model based on heat transfer equilibrium among the air flow, the floor and the indoor air. The time variations in the indoor air temperature for the serial duct floor heating system were investigated theoretically and experimentally. The time variations in the floor surface and the indoor air temperatures were predicted theoretically for the parallel duct floor heating system. Experiments on the time variations of the dimensionless numbers such as Nu for the airflow in duct and the indoor air, Gr for the indoor air and the heat ratios of convection and radiation to total heat for the serial duct floor heating system were performed. The theoretical and experimental results showed a good agreement. (C) 2004 Elsevier B.V. All rights reserved.
引用
收藏
页码:579 / 586
页数:8
相关论文
共 10 条
[1]   Investigation of thermal performance of a passive solar building with floor radiant heating [J].
Athienitis, AK .
SOLAR ENERGY, 1997, 61 (05) :337-345
[2]  
BOZKOR O, 2002, THESIS ERCIYES U KAY
[3]   An experimental study of multiple parameter switching control for radiant floor heating systems [J].
Cho, SH ;
Zaheer-Uddin, M .
ENERGY, 1999, 24 (05) :433-444
[4]  
Chun WG, 1999, INT J ENERG RES, V23, P335, DOI 10.1002/(SICI)1099-114X(19990325)23:4<335::AID-ER483>3.0.CO
[5]  
2-7
[6]  
De Carlo JP, 1984, FUNDAMENTALS FLOW ME
[7]  
Incropera F.P., 1990, FUNDAMENTALS HEAT MA
[8]   AN ACTIVE CHARGE, PASSIVE DISCHARGE FLOOR SPACE HEATING-SYSTEM [J].
SALT, H ;
MAHONEY, KJ .
SOLAR ENERGY, 1987, 38 (01) :25-31
[9]  
TEKIN Y, 1999, THESIS ERCIYES U KAY
[10]   Optimal operation of an embedded-piping floor heating system with control input constraints [J].
ZaheerUddin, M ;
Zheng, GR ;
Cho, SH .
ENERGY CONVERSION AND MANAGEMENT, 1997, 38 (07) :713-725