Enhanced Fault Ride-Through Method for Wind Farms Connected to the Grid Through VSC-Based HVDC Transmission

被引:187
作者
Feltes, Christian [1 ]
Wrede, Holger [2 ]
Koch, Friedrich W. [3 ]
Erlich, Istvan [1 ]
机构
[1] Univ Duisburg Essen, Dept Elect Power Syst, Duisburg, Germany
[2] EON Engn GmbH, Gelsenkirchen, Germany
[3] REpower Syst AG, Rendsburg, Germany
关键词
Doubly fed induction generator (DFIG); fault ride-through (FRT); high voltage DC transmission (HVDC); offshore wind farm; voltage source converter (VSC);
D O I
10.1109/TPWRS.2009.2023264
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper describes a new control approach for secure fault-ride through of wind farms connected to the grid through a voltage source converter-based high voltage DC transmission. On fault occurrence in the high voltage grid, the proposed control initiates a controlled voltage drop in the wind farm grid to achieve a fast power reduction. In this way overvoltages in the DC transmission link can be avoided. It uses controlled demagnetization to achieve a fast voltage reduction without producing the typical generator short circuit currents and the related electrical and mechanical stress to the wind turbines and the converter. The method is compared to other recent FRT methods for HVDC systems and its superior performance is demonstrated by simulation results.
引用
收藏
页码:1537 / 1546
页数:10
相关论文
共 14 条
[1]  
*ABB, 2006, TECHN DESCR HDVD LIG
[2]  
E.ON Netz GmbH, 2006, NETZ HOCH HOCHSTSP
[3]  
ERLICH I, 2007, P 2007 IEEE POW CONV
[4]   Modeling of wind turbines based on doubly-fed induction generators for power system stability studies [J].
Erlich, Istvan ;
Kretschmann, Joerg ;
Fortmann, Jens ;
Mueller-Engelhardt, Stephan ;
Wrede, Holger .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2007, 22 (03) :909-919
[5]  
FELTES C, P 2008 PSCC 16 POW S
[6]  
Feltes C., P 2006 IEEE POW ENG
[7]  
Harnefors L., RIDE THROUGH METHODS
[8]  
JIANGHAFNER Y, 2002, P 2002 IEEE TRANSM D
[9]  
Ming Y., P 2006 IEEE INT C PO
[10]  
PENA R, P 1996 IEE EL POW AP