Particular characteristics of transcritical CO2 refrigeration cycle with an ejector

被引:208
作者
Deng, Jian-qiang
Jiang, Pei-xue [1 ]
Lu, Tao
Lu, Wei
机构
[1] Tsinghua Univ, Dept Thermal Engn, Key Lab Thermal Sci & Power Engn, Beijing 100084, Peoples R China
[2] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Dept Proc Equipment & Control Engn, Xian 710049, Peoples R China
关键词
refrigeration system; transcritical cycle; CO2; ejector;
D O I
10.1016/j.applthermaleng.2006.07.016
中图分类号
O414.1 [热力学];
学科分类号
摘要
The present study describes a theoretical analysis of a transcritical CO2 ejector expansion refrigeration cycle (EERC) which uses an ejector as the main expansion device instead of an expansion valve. The system performance is strongly coupled to the ejector entrainment ratio which must produce the proper CO2 quality at the ejector exit. If the exit quality is not correct, either the liquid will enter the compressor or the evaporator will be filled with vapor. Thus, the ejector entrainment ratio significantly influences the refrigeration effect with an optimum ratio giving the ideal system performance. For the working conditions studied in this paper, the ejector expansion system maximum cooling COP is up to 18.6% better than the internal heat exchanger cycle (IHEC) cooling COP and 22.0% better than the conventional vapor compression refrigeration cycle (VCRC) cooling COP. At the conditions for the maximum cooling COP, the ejector expansion cycle refrigeration output is 8.2% better than the internal heat exchanger cycle refrigeration output and 11.5% better than the conventional cycle refrigeration output. An exergy analysis showed that the ejector expansion cycle greatly reduces the throttling losses. The analysis was also used to study the variations of the ejector expansion cycle cooling COP for various heat rejection pressures, refrigerant temperatures at the gas cooler exit, nozzle efficiencies and diffuser efficiencies. (c) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:381 / 388
页数:8
相关论文
共 13 条
[1]   A verification study of steam-ejector refrigeration model [J].
Alexis, GK ;
Rogdakis, ED .
APPLIED THERMAL ENGINEERING, 2003, 23 (01) :29-36
[2]   Experimental investigation on the performance of the refrigeration cycle using a two-phase ejector as an expansion device [J].
Disawas, S ;
Wongwises, S .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (06) :587-594
[3]  
Domanski P.A., 1995, NISTIR5606
[4]  
Fan X. W., 1996, J XIAN JIAOTONG U, V30, P5
[5]  
Fan X. W., 1997, J XIAN JIAOTONG U, V31, P6
[6]  
Harrell GS, 1995, PROCEEDINGS OF THE 30TH INTERSOCIETY ENERGY CONVERSION ENGINEERING CONFERENCE, VOLS 1-3, pC49
[7]  
Kornhauser A. A., 1990, P 1990 USNC IIR PURD, P10, DOI DOI 10.1109/IECEC.1990.747930
[8]   A correlation of optimal heat rejection pressures in transcritical carbon dioxide cycles [J].
Liao, SM ;
Zhao, TS ;
Jakobsen, A .
APPLIED THERMAL ENGINEERING, 2000, 20 (09) :831-841
[9]  
[刘军朴 Liu Junpu], 2004, [上海交通大学学报, Journal of Shanghai Jiaotong University], V38, P273
[10]  
Menegay P, 1996, PROC IECEC, P702, DOI 10.1109/IECEC.1996.553783