Fault ride through of fully rated converter wind turbines with AC and DC transmission systems

被引:112
作者
Ramtharan, G. [1 ]
Arulampalam, A. [2 ]
Ekanayake, J. B. [2 ,3 ]
Hughes, F. M.
Jenkins, N. [3 ]
机构
[1] Garrad Hassan & Partners Ltd, St Vincents Works, Bristol BS2 0QD, Avon, England
[2] Univ Peradeniya, Fac Engn, Dept Elect & Elect Engn, Peradeniya 20400, Sri Lanka
[3] Cardiff Univ, Cardiff Sch Engn, Ctr Integrated Renewable Energy Generat & Supply, Cardiff CF24 3AA, S Glam, Wales
基金
英国工程与自然科学研究理事会;
关键词
D O I
10.1049/iet-rpg.2008.0018
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Fault ride through of fully rated converter wind turbines in an offshore wind farm connected to onshore network via either high voltage AC (HVAC) or high voltage DC (HVDC) transmission is described. Control of the generators and the grid side converters is shown using vector control techniques. A de-loading scheme was used to protect the wind turbine DC link capacitors from over voltage. How de-loading of each generator aids the fault ride through of the wind farm connected through HVAC transmission is demonstrated. The voltage recovery of the AC network during the fault was enhanced by increasing the reactive power current of the wind turbine grid side converter. A practical fault ride through protection scheme for a wind farm connected through an HVDC link is to employ a chopper circuit on the HVDC link. Two alternatives to this approach are also discussed. The first involves de-loading the wind farm on detection of the fault, which requires communication of the fault condition to each wind turbine of the wind farm. The second scheme avoids this complex communication requirement by transferring the fault condition via control of the HVDC link to the offshore converter. The fault performances of the three schemes are simulated and the results were used to assess their respective capabilities.
引用
收藏
页码:426 / 438
页数:13
相关论文
共 28 条
[1]  
Ackermann T., 2002, IEEE Power Engineering Review, V22, P23, DOI 10.1109/MPER.2002.1098040
[2]  
Ackermann T, 2005, WIND POWER IN POWER SYSTEMS, P1, DOI 10.1002/0470012684
[3]   Variable-speed wind turbines with multi-pole synchronous permanent magnet generators. Part I: Modelling in dynamic simulation tools [J].
Akhmatov, Vladislav ;
Nielsen, Arne Hejde ;
Pedersen, J. Kaas ;
Nymann, Ole .
Wind Engineering, 2003, 27 (06) :531-548
[4]   Modelling and ride-through capability of variable speed wind turbines with permanent magnet generators [J].
Akhmatov, Vladislav .
WIND ENERGY, 2006, 9 (04) :313-326
[5]  
[Anonymous], GRID COD HIGH EXTR H
[6]  
Bossanyi E. A., 2000, Wind energy, V3, P149, DOI [10.1002/we.34.abs, DOI 10.1002/WE.34.ABS]
[7]  
Eriksson K., SYSTEM APPROACH DESI
[8]  
GABRIELE M, 2007, EWEC 2007 C MILL 7 1
[9]  
HARNEFORS L, 2007, NORD WIND POW C RIS
[10]  
HARTGE F, 2006, FACTS CAPABILITIES W