Data reduction for air-side performance of fin-and-tube heat exchangers

被引:126
作者
Wang, CC
Webb, RL [1 ]
Chi, KY
机构
[1] Penn State Univ, Dept Mech Engn, University Pk, PA 16802 USA
[2] Ind Technol Res Inst, Energy & Resources Labs, Mito, Ibaraki 310, Japan
关键词
heat exchangers; fin and tube; HVAC;
D O I
10.1016/S0894-1777(00)00005-4
中图分类号
O414.1 [热力学];
学科分类号
摘要
The present study focuses on the data reduction method to obtain the air-side performance of fin-and-tube heat exchangers. The data reduction methodology for air-side heat transfer coefficients in the literature is not based on a consistent approach. This paper recommends standard procedures for dry surface heat transfer in finned-tube heat exchangers having water on the tube-side. Inconsistencies addressed include the epsilon-NTU relationships, calculation of the tube-side heat transfer coefficient, calculation of lin efficiency, and whether entrance and exit loss should be included in the reduction of friction factors. Use of the recommended standardized methodology will provide more meaningful data for use in the development of correlations, or for performance comparison purposes. (C) 2000 Elsevier Science inc. All rights reserved.
引用
收藏
页码:218 / 226
页数:9
相关论文
共 23 条
[1]  
[Anonymous], 1991, 86018 ESDU, P92
[2]  
[Anonymous], P 3 ASME JSME THERM
[3]  
[Anonymous], 1978, ASHRAE Trans
[4]  
[Anonymous], 1973, ASHRAE T
[5]  
*ASHRAE, 1978, 3378 ASHRAE
[6]  
GNIELINSKI V, 1976, INT CHEM ENG, V16, P359
[7]  
Hatada T., 1989, ASHRAE T, V95, P166
[8]  
HONG TK, 1996, INT J HVAC R RES, V2, P27
[9]   Effect of strip location on the air-side pressure drop and heat transfer in strip fin-and-tube heat exchanger [J].
Kang, HC ;
Kim, MH .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (04) :302-312
[10]  
Kang HC, 1999, COMPACT HEAT EXCHANGERS AND ENHANCEMENT TECHNOLOGY FOR THE PROCESS INDUSTRIES, P217