Distribution line carrier: Analysis procedure and applications to DG

被引:40
作者
Benato, Roberto [1 ]
Caldon, Roberto [1 ]
机构
[1] Univ Padua, Dept Elect Engn, I-35131 Padua, Italy
关键词
dispersed generation; distribution line carrier; high-frequency propagation; islanding; medium-voltage (MV) networks;
D O I
10.1109/TPWRD.2006.877089
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
This paper deals with the analysis of carrier signal transmission in medium-voltage (MV) distribution networks. A multiconductor matrix procedure based on the bus admittance matrix, which accounts for the earth return currents, enables predicting the high-frequency behavior of the distribution networks and, hence, the effectiveness of transmitted signals. To this aim, suitable models have been implemented based on the Carson's theory for overhead lines with ground return and Wedepohl's theory for cable lines. A comparison with the modal analysis demonstrates the advantages of the multiconductor matrix algorithm with respect to the modal analysis. In order to validate the theoretical results, two measurement campaigns have been carried out on real MV networks. A good agreement between measured and computed values has been verified. Since distribution networks are generally unlike each other, the procedure becomes a valuable tool, which makes it easy to assess the feasibility of distribution line carrier (DLC) applications in any system. In particular, a protection system to prevent the islanding of dispersed generators is proposed. In addition, in a foreseeable hypothesis of allowed islanding operation of portions of distribution networks (microgrids), DLCs are proposed as communication control of the interface device at the point of common coupling.
引用
收藏
页码:575 / 583
页数:9
相关论文
共 8 条
[1]
A GENERAL FORMULATION OF IMPEDANCE AND ADMITTANCE OF CABLES [J].
AMETANI, A .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (03) :902-910
[2]
ANALYSIS OF DISTRIBUTION LINE CARRIER PROPAGATION USING THE BUS IMPEDANCE MATRIX [J].
AMOURA, FK ;
ONEAL, JB .
IEEE TRANSACTIONS ON POWER DELIVERY, 1987, 2 (04) :976-984
[3]
Arrilaga J., 1985, POWER SYSTEM HARMONI
[4]
Benato R, 1998, INT C HARMON QUAL PO, P359, DOI 10.1109/ICHQP.1998.759913
[5]
BENATO R, 2003, P 17 INT C EL DISTR
[6]
*CCITT, 1989, DIR CONC PROT TEL LI
[7]
THE EFFECT OF DISTRIBUTION TRANSFORMERS ON DISTRIBUTION LINE CARRIER SIGNALS [J].
HEMMINGER, RC ;
GALE, LJ ;
AMOURA, F ;
ONEAL, JB .
IEEE TRANSACTIONS ON POWER DELIVERY, 1987, 2 (01) :36-40
[8]
TRANSIENT ANALYSIS OF UNDERGROUND POWER-TRANSMISSION SYSTEMS - SYSTEM-MODEL AND WAVE-PROPAGATION CHARACTERISTICS [J].
WEDEPOHL, LM ;
WILCOX, DJ .
PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1973, 120 (02) :253-260