Parameter Design of a Two-Current-Loop Controller Used in a Grid-Connected Inverter System With LCL Filter

被引:217
作者
Liu, Fei
Zhou, Yan [1 ]
Duan, Shanxu [1 ]
Yin, Jinjun [1 ]
Liu, Bangyin [1 ]
Liu, Fangrui [1 ]
机构
[1] Huazhong Univ Sci & Technol, Dept Appl Power Elect Engn, Wuhan 430074, Peoples R China
关键词
Grid connected; LCL filter; renewable energy generation; two-current-loop controller; CONTROL STRATEGY;
D O I
10.1109/TIE.2009.2021175
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
LCL filters offer a better choice of attenuating switching frequency harmonics. However, in a grid-connected system, an LCL filter may cause resonance which is a disaster for the system's stability. In order to solve the problem, a two-current-loop control strategy, which includes grid-current outer loop and filter-capacitor-current inner loop, is adopted here. The implementation of this strategy is easy, but the tuning procedure is complex since the outer and inner controllers cannot cooperate well if the parameters of the controllers are not suitable. There is no literature which mentions a method to help give out accurate parameters of the controller. The difficulty of designing the controller is that only two feedbacks cannot provide complete information of a three-order LCL filter. A specific method is proposed in this paper to design the controller. The advantage of this method is to provide a way to maximize the utilization of the two feedbacks to get good system performance through parameter determination. The practicability of the method is tested by using bode diagram, and the antidistortion ability of the system is analyzed. Finally, experimental results verify the availability and correctness of the proposed method.
引用
收藏
页码:4483 / 4491
页数:9
相关论文
共 22 条
[1]   Renewable energy systems with photovoltaic power generators: Operation and modeling [J].
Bialasiewicz, Jan T. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2008, 55 (07) :2752-2758
[2]   A novel control to actively damp resonance in input LC filter of a three-phase voltage source converter [J].
Blasko, V ;
Kaura, V .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (02) :542-550
[3]  
GULLVIK W, 2007, P EUR C POW EL APPL, P1
[4]   Stability of photovoltaic and wind turbine grid-connected inverters for a large set of grid impedance values [J].
Liserre, M ;
Teodorescu, R ;
Blaabjerg, F .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2006, 21 (01) :263-272
[5]   Design and control of an LCL-filter-based three-phase active rectifier [J].
Liserre, M ;
Blaabjerg, F ;
Hansen, S .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2005, 41 (05) :1281-1291
[6]   Genetic algorithm-based design of the active damping for an LCL-filter three-phase active rectifier [J].
Liserre, M ;
Dell'Aquila, A ;
Blaabjerg, F .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2004, 19 (01) :76-86
[7]   Stability improvements of an LCL-filter based three-phase active rectifier [J].
Liserre, M ;
Dell'Aquila, A ;
Blaabjerg, F .
PESC'02: 2002 IEEE 33RD ANNUAL POWER ELECTRONICS SPECIALISTS CONFERENCE, VOLS 1-4, CONFERENCE PROCEEDINGS, 2002, :1195-1201
[8]  
LIU F, 2007, P IEEE IECON, P1656
[9]  
Magueed FA, 2005, IEEE IND APPLIC SOC, P572
[10]   A simple voltage sensorless active damping scheme for three-phase PWM converters with an LCL filter [J].
Malinowski, Mariusz ;
Bemet, Steffen .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2008, 55 (04) :1876-1880