The influence of area-specific ventilation rate on the emissions from construction products

被引:13
作者
Gunnarsen, L
机构
[1] Danish Building Research Institute, Box 119
来源
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE | 1997年 / 7卷 / 02期
关键词
emissions from construction products; perceived air quality; VOC; ventilation rate; environmental parameters;
D O I
10.1111/j.1600-0668.1997.t01-2-00005.x
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Experiments were performed using small-scale climate chambers, including the new Chamber for Laboratory Investigations of Materials Pollution and Air Quality (CLIMPAQ), to gain knowledge about the influence of ventilation rate per plane specimen area (specific ventilation rate) on emission rates. Emissions from pieces of linoleum, waterborne acrylic paint, nylon carpet, and sealant were quantified at different specific ventilation rates. A trained sensory panel used the decipol scale and chemical analysis quantified some major Volatile Organic Compounds (VOCs) after the specimens had been conditioned in the chambers for six days. The results showed that the specific ventilation rate (L/s m2) may influence the emission rates. In both sensory and chemical terms, emission rates increased when ventilation was increased. At low specific ventilation rates the emission rate was proportional to the specific ventilation rate. For higher ventilation rates the emission rates stabilized and became independent of ventilation. The chemical measurements showed that only the emissions from the tested paint were influenced by ventilation rates above those comparable to 0.5 h(-1) in a typical room. The emissions quantified by the sensory panel continued, however, to be influenced by ventilation even at rates higher than 5 h(-1). (C) Indoor Air (1997).
引用
收藏
页码:116 / 120
页数:5
相关论文
共 10 条
[1]  
Bluyssen PM., 1991, INDOOR AIR, V1, P414, DOI DOI 10.1111/J.1600-0668.1991.00005.X
[2]  
EKBERG LE, 1995, P HLTH BUILD 95, V3, P1353
[3]  
GIRMAN JR, 1989, OCCUP MED, V4, P695
[4]   DESIGN AND CHARACTERIZATION OF THE CLIMPAQ, CHAMBER FOR LABORATORY INVESTIGATIONS OF MATERIALS, POLLUTION AND AIR-QUALITY [J].
GUNNARSEN, L ;
NIELSEN, PA ;
WOLKOFF, P .
INDOOR AIR, 1994, 4 (01) :56-62
[5]  
KNUDSEN HN, 1994, THESIS TU DENMARK
[6]  
NIELSEN PA, 1988, P HEALTHY BUILDINGS, V3, P391
[7]  
PEJTERSEN J, 1993, P INDOOR AIR 93 HELS, V1, P95
[8]   THE EFFECT OF VENTILATION ON EMISSION RATES OF WOOD FINISHING MATERIALS [J].
TICHENOR, BA ;
GUO, ZS .
ENVIRONMENT INTERNATIONAL, 1991, 17 (04) :317-323
[9]  
Wolkoff P, 1991, INDOOR AIR, V4, P478, DOI [10.1111/j.1600-0668.1991.00012.x, DOI 10.1111/J.1600-0668.1991.00012.X]
[10]  
Wolkoff P., 1991, P HLTH BUILD ASHRAE, P160