Structure optimization of energy supply systems in tertiary sector buildings

被引:122
作者
Lozano, Miguel A. [1 ]
Ramos, Jose C. [1 ]
Carvalho, Monica [1 ]
Serra, Luis M. [1 ]
机构
[1] Univ Zaragoza, Dept Mech Engn, Grp GITSE I3A, Zaragoza 50018, Spain
关键词
Trigeneration; CHCP; Cogeneration; CHP; Optimization; MILP; Energy; Building; Hospital; TURBINE COGENERATION PLANTS; DESIGN; PURPOSE; POWER; HEAT;
D O I
10.1016/j.enbuild.2009.05.008
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Trigeneration systems, also known as Combined Heat, Cooling and Power (CHCP) systems, are interesting alternatives to supply different energy services in urban districts and in large buildings, particularly in warm areas such as Mediterranean countries. These systems can provide substantial benefits from economic, energetic, and environmental viewpoints, since the cogenerated heat can be used for heating in winter as well as cooling in summer with an absorption refrigerator. This paper develops an optimization model using Mixed Integer Linear Programming (MILP) to determine the type, number and capacity of equipment in CHCP systems installed in the tertiary sector as well as to establish the optimal operation mode for the different plant components on an hour-by-hour basis throughout the The objective function to be minimized is the annual total cost. The optimization model considers year. the legal constraints imposed to feed the surplus autogenerated electricity into the grid at a regulated feed-in tariff. The optimization model is applied to design a system providing energy services for a hospital located in the city of Zaragoza (Spain). The effects of the financial market conditions and energy prices in the optimal structure of the system are analyzed. (C) 2009 Elsevier B.V. All rights reserved.
引用
收藏
页码:1063 / 1075
页数:13
相关论文
共 49 条
[1]  
[Anonymous], 1999, WIL INT S D
[2]   Retrospective on optimization [J].
Biegler, LT ;
Grossmann, IE .
COMPUTERS & CHEMICAL ENGINEERING, 2004, 28 (08) :1169-1192
[3]  
BROWN TR, 2000, CAPITAL COST ESTIMAT, P93
[4]   A rigorous MINLP model for the optimal synthesis and operation of utility plants [J].
Bruno, JC ;
Fernandez, F ;
Castells, F ;
Grossmann, LE .
CHEMICAL ENGINEERING RESEARCH & DESIGN, 1998, 76 (A3) :246-258
[5]   Thermal integration of trigeneration systems [J].
Calva, ET ;
Núñez, MP ;
Toral, MAR .
APPLIED THERMAL ENGINEERING, 2005, 25 (07) :973-984
[6]   Assessment of the greenhouse gas emissions from cogeneration and trigeneration systems. Part I: Models and indicators [J].
Chicco, Gianfranco ;
Mancarella, Pierluigi .
ENERGY, 2008, 33 (03) :410-417
[7]   Distributed multi-generation: A comprehensive view [J].
Chicco, Gianfranco ;
Mancarefla, Pierluigi .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2009, 13 (03) :535-551
[8]  
CHOSE, 2001, EN SAV COMB HEAT COO
[9]  
CONSTANTINESCU N, 2003, DISTRICT HEATING EUR, P57
[10]   Exergy cost analysis of a micro-trigeneration system based on the structural theory of thermoeconomics [J].
Deng, Jian ;
Wang, Ruzhu ;
Wu, Jingyi ;
Han, Guyong ;
Wu, Dawei ;
Li, Sheng .
ENERGY, 2008, 33 (09) :1417-1426