DSTRP:: A new algorithm for high impedance fault detection in compensated neutral grounded MV power systems

被引:6
作者
Ruz, F
Quijano, A
Gómez, E
机构
[1] Univ Politecn Cartagena, Dept Ingn Elect, Cartagena 30201, Spain
[2] Univ Politecn Valencia, Edificio Inst 2, Inst Tecnol Elect, Valencia 46022, Spain
[3] Univ Politecn Cartagena, Dept Ingn Elect, Cartagena Murcia 30202, Spain
来源
EUROPEAN TRANSACTIONS ON ELECTRICAL POWER | 2003年 / 13卷 / 01期
关键词
D O I
10.1002/etep.4450130104
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The detection algorithms depend on the network topology, the neutral grounding of the secondary winding in H.V./M.V. transformers being one of the main factors to consider. In compensated distribution systems, we need complex detection algorithms based on network parameters estimation. The neutral voltage is the most sensitive magnitude to detect an unusual situation but it is not a selective parameter. In this paper we present the new DSTRP that calculates the influence of each feeder asymmetry in neutral voltage. We also analyze the measurement errors influence that limits the sensitivity threshold of this algorithm.
引用
收藏
页码:23 / 28
页数:6
相关论文
共 7 条
[1]  
Bisiach L., 1996, Energia Elettrica, V73, P457
[2]  
CLEMENT M, 1991, RGE REV GEN ELECT, V91, P50
[3]  
CLEMENT M, 1992, 2 INT C POW QUAL PQA
[4]  
LEITLOFF V, 1996, ETEP, V4, P145
[5]  
RUZ F, 1997, GABINETE INFORMACION, V97, P162
[6]  
RUZ F, 1999, THESIS U POLITECNICA
[7]  
Welfonder T., 1997, 32nd Universities Power Engineering Conference. UPEC '97, P947