Exploiting voltage support of voltage-source HVDC

被引:24
作者
Huang, Z [1 ]
Ooi, BT
Dessaint, LA
Galiana, FD
机构
[1] Univ Alberta, Dept Elect & Comp Engn, Edmonton, AB T6G 2V4, Canada
[2] McGill Univ, Dept Elect & Comp Engn, Montreal, PQ H3A 2A7, Canada
[3] Ecole Technol Super, Dept Elect Engn, Montreal, PQ H3C 1K3, Canada
关键词
D O I
10.1049/ip-gtd:20030099
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The inherent voltage support in voltage-source converters (VSCs) which form a back-to-back VSC-HVDC asynchronous link can increase the power transmissibility by a factor of 1.68 if the installation is sited at the midpoint of the radial AC transmission line. The figure of 1.68 is the limit set by the 'transient stability' which is reached by simulations using HYPERSIM, a real-time digital simulator. The transmission line is modelled by the telegraph equations. The hydraulic turbine, speed governor, generator, field-excitation system, power-system stabiliser (PSS) and transformers are modelled in detail.