Experimental investigation on influence of smoke venting velocity and vent height on mechanical smoke exhaust efficiency

被引:55
作者
Jie, Ji [2 ]
Kaiyuan, Li [3 ]
Wei, Zhong [1 ]
Ran, Huo [2 ]
机构
[1] Zhengzhou Univ, Sch Chem Engn, Zhengzhou 450001, Peoples R China
[2] Univ Sci & Technol Chin, State Key Lab Fire Sci, Hefei 230026, Peoples R China
[3] Univ Canterbury, Dept Civil & Nat Resources Engn, Christchurch 8140, New Zealand
关键词
Smoke exhausting efficiency; Smoke vent height; Exhausting velocity; Plug-holing;
D O I
10.1016/j.jhazmat.2009.12.019
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A set of burning experiments were conducted to investigate the influence of smoke vent height and exhausting velocity on mechanical smoke exhausting efficiency. Results have shown that the smoke exhausting process becomes more efficient due to the increased smoke vent height and the decreased exhausting velocity, which eliminate the plug-holing issue with fewer disturbances on the smoke layer interface. For each certain exhausting velocity, there is a critical value of distance between the vent and the bottom of the smoke layer. When the distance is less than the critical value, the smoke exhausting is inefficient, and the efficiency decreases sharply as the distance decreases. Contrarily, when the distance is greater than the critical value, a good efficiency can be acquired and the exhausted smoke increased relatively slowly as the distance increases. A critical Froude number, proposed by Hinkley to predict the onset of plug-holing effect in gravity venting systems, was validated in the experiments. However, the experimental results indicate that in the tests without the plug-holing, the fresh air entrained due to smoke exhausting is up to 48% of the mechanical exhausting rate. Crown Copyright (C) 2009 Published by Elsevier BM. All rights reserved.
引用
收藏
页码:209 / 215
页数:7
相关论文
共 17 条
[1]   A methodology for obtaining and using toxic potency data for fire hazard analysis [J].
Babrauskas, V ;
Gann, RG ;
Levin, BC ;
Paabo, M ;
Harris, RH ;
Peacock, RD .
FIRE SAFETY JOURNAL, 1998, 31 (04) :345-358
[2]  
Besserre R., 1997, Urgences Medicales, V16, P77, DOI 10.1016/S0923-2524(97)88674-2
[3]  
Cooper L.Y., 2002, SFPE HDB FIRE PROTEC
[4]   ENGINEERING RELATIONS FOR FIRE PLUMES [J].
HESKESTAD, G .
FIRE SAFETY JOURNAL, 1984, 7 (01) :25-32
[5]  
Hietaniemi J, 1999, FIRE MATER, V23, P171, DOI 10.1002/(SICI)1099-1018(199907/08)23:4<171::AID-FAM680>3.0.CO
[6]  
2-C
[7]   Full-scale experimental studies on mechanical smoke exhaust efficiency in an underground corridor [J].
Hu, L. H. ;
Li, Y. Z. ;
Huo, R. ;
Yi, L. ;
Chow, W. K. .
BUILDING AND ENVIRONMENT, 2006, 41 (12) :1622-1630
[8]  
Lougheed GD, 2001, ASHRAE J, V43, P34
[9]   MOMENTUM IMPLICATIONS FOR BUOYANT DIFFUSION FLAMES [J].
MCCAFFREY, BJ .
COMBUSTION AND FLAME, 1983, 52 (02) :149-167
[10]  
*MIN CONSTR PR CHI, 2003, COD DES SUBW GB 5015