Application of desiccant wheel to control humidity in air-conditioning systems

被引:78
作者
Subramanyam, N [1 ]
Maiya, MP [1 ]
Murthy, SS [1 ]
机构
[1] Indian Inst Technol, Dept Mech Engn, Refrigerat & Air Conditioning Lab, Madras 600036, Tamil Nadu, India
关键词
desiccant wheel; humidity control; dehumidification; air-conditioning;
D O I
10.1016/j.applthermaleng.2004.04.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
Control of relative humidity is an essential aspect of maintaining indoor air quality in an air-conditioned space. In this paper, a desiccant wheel integrated air-conditioner is studied for low humidity air-conditioning. The desiccant wheel dehumidifies and heats the supply air. The regeneration of desiccant is accomplished by the return air, which gets cooled and humidified. The study shows that the proposed system can deliver supply air at much lower dew point temperature compared to the conventional system with a marginal penalty on COP. Its performance is better than the typical reheat system to provide the same low humidity levels. (C) 2004 Published by Elsevier Ltd.
引用
收藏
页码:2777 / 2788
页数:12
相关论文
共 11 条
  • [1] *ASHRAE, 1997, HDB FUND
  • [2] ASHRAE, 1995, HDB HVAC APPL
  • [3] AZAR JAA, 2000, ASHRAE T, V106, P95
  • [4] Belding WA, 1997, ASHRAE TRAN, V103, P841
  • [5] DHAR PL, 1998, IIR C EN TRENDS R A
  • [6] The potential of solar energy use in desiccant cooling cycles
    Henning, HM
    Erpenbeck, T
    Hindenburg, C
    Santamaria, IS
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (03): : 220 - 229
  • [7] Measurements of effectiveness in a silica gel rotary exchanger
    Neti, S
    Wolfe, EI
    [J]. APPLIED THERMAL ENGINEERING, 2000, 20 (04) : 309 - 322
  • [8] NIMMO BG, 1993, ASHRAE TRAN, V99, P842
  • [9] SHIREY DB, 1993, ASHRAE TRAN, V99, P694
  • [10] Stoecker W. F., 1982, REFRIGERATION AIR CO