Transfer function method to diagnose axial displacement and radial deformation of transformer windings

被引:256
作者
Rahimpour, E [1 ]
Christian, J
Feser, K
Mohseni, H
机构
[1] Univ Stuttgart, Inst Power Transmiss & High Voltage Technol, D-70569 Stuttgart, Germany
[2] Univ Tehran, Fac Engn, Dept Elect Engn, Tehran 14399, Iran
关键词
diagnose; mechanical displacements; modeling; transfer function; transformer windings;
D O I
10.1109/TPWRD.2003.809692
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Short circuit currents or forces during transport can cause mechanical displacements of transformer windings. The transfer function method is presented as a tool to detect these displacements. In order to be able to evaluate the measurements, the correlation between the characteristics of transfer functions and possible damages must be known. Axial displacement and radial deformation of transformer windings have been studied in this research work using two test transformers. The primary winding of the first transformer for axial displacement has 31 double disk coils (1.3 MVA, 10 kV) and the secondary winding is a four layer winding. The second transformer for the study of radial deformation has 30 double disk coils (1.2 MVA, 10 kV) as primary winding and a one layer winding as secondary winding. The detailed mathematical models were developed for the test objects and a comparison was carried out between measured and calculated results. It is shown that this model can present the behavior of the transformer windings in the frequency domain in the case of sound and displaced conditions.
引用
收藏
页码:493 / 505
页数:13
相关论文
共 23 条
[1]  
[Anonymous], ARCH ELEKTROTECHNIK
[2]  
[Anonymous], 2000, 123304 CIGRE
[3]   TRANSIENT SIMULATION AND ANALYSIS OF A 3-PHASE 5-LIMB STEP-UP TRANSFORMER FOLLOWING AN OUT-OF-PHASE SYNCHRONIZATION [J].
ARTURI, CM .
IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (01) :196-201
[4]   MATRIX REPRESENTATION OF 3-PHASE N-WINDING TRANSFORMERS FOR STEADY-STATE AND TRANSIENT STUDIES [J].
BRANDWAJN, V ;
DOMMEL, HW ;
DOMMEL, II .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (06) :1369-1378
[5]  
BUCKOW E, 1986, BERECHNUNG VERHALTEN
[6]  
CHRISTIAN J, 1999, P 11 INT S HIGH VOLT, V1, P37
[7]   TIME DOMAIN MODELING OF EDDY-CURRENT EFFECTS FOR TRANSFORMER TRANSIENTS [J].
DELEON, F ;
SEMLYEN, A ;
ARTURI, CM ;
NARANG, A ;
DICK, EP .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (01) :271-280
[8]  
DELEON F, 1994, IEEE T POWER DELIVER, V9, P231, DOI 10.1109/61.277694
[9]  
DIETRICH W, 1988, ETZ ARCHIV, V10, P309
[10]   Hybrid modelling of inhomogeneous transformer windings for very fast transient overvoltage studies [J].
Gharehpetian, GB ;
Mohseni, H ;
Moller, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 1998, 13 (01) :157-163