Control strategy and experimental study on a novel defrosting method for air-source heat pump

被引:39
作者
Liang, Cai-Hua [1 ]
Zhang, Xiao-Song [1 ]
Li, Xiu-Wei [1 ]
Chen, Zhen-Qian [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Peoples R China
关键词
Defrosting method; Control strategy; Self-organizing fuzzy control; Air-source heat pump; FROST FORMATION; CROSS-FLOW; PLATE; PERFORMANCE; EVAPORATOR; CYLINDER; SURFACE; SYSTEM; MODEL;
D O I
10.1016/j.applthermaleng.2009.12.022
中图分类号
O414.1 [热力学];
学科分类号
摘要
A new defrosting method - the sensible heat defrosting method, aiming at shelving the various disadvantages of the conventional reverse cycle defrosting was proposed in this paper. The mechanism and process of this method was analysed. To guarantee the reliability, the self-organizing control algorithm with self-learning function was introduced based on the cardinal fuzzy control algorithm. Moreover, the control strategy was enacted; the corresponding self-organizing fuzzy control system was developed; the Micro Controller Unit (MCU) based control unit was accomplished; and the experimental study was conducted to investigate the sample machine of air-source heat pump system. The results of the experiments showed that the self-organizing control algorithm has good control characteristic and effect. On one hand, the adverse shock from the conventional reverse cycle defrosting to the refrigeration system could be avoided through this proposed method; on the other hand, the "oil rush" could also be eliminated. Besides, the thermal comfort could be greatly improved since the temperature fluctuation range of the supplied water is narrowed by applying this new method in practice. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:892 / 899
页数:8
相关论文
共 18 条
[1]  
CGAWA K, 1993, ASHRAE T, V99, P662
[2]   Performance of a showcase refrigeration system with multi-evaporator during on-off cycling and hot-gas bypass defrost [J].
Cho, HY ;
Kim, YC ;
Jang, IK .
ENERGY, 2005, 30 (10) :1915-1930
[3]   Study of free convection frost formation on a vertical plate [J].
Fossa, M ;
Tanda, G .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2002, 26 (6-7) :661-668
[4]  
Han Zhi-tao, 2007, Journal of Harbin Institute of Technology, V39, P901
[5]  
Hayashi K., 1977, J HEAT TRANSFER, V99, P239
[6]   Hot gas defrost model development and validation [J].
Hoffenbecker, N ;
Klein, SA ;
Reindl, DT .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (04) :605-615
[7]   Proposed energy-efficient air-conditioning system using liquid desiccant [J].
Kinsara, AA ;
Elsayed, MM ;
AlRabghi, OM .
APPLIED THERMAL ENGINEERING, 1996, 16 (10) :791-806
[8]   PERFORMANCE OF FINNED-TUBE HEAT-EXCHANGERS UNDER FROSTING CONDITIONS .2. COMPARISON OF EXPERIMENTAL-DATA WITH MODEL [J].
KONDEPUDI, SN ;
ONEAL, DL .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1993, 16 (03) :181-184
[9]   Frost formation on a plate with different surface hydrophilicity [J].
Lee, H ;
Shin, J ;
Ha, S ;
Choi, B ;
Lee, J .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2004, 47 (22) :4881-4893
[10]   An experimental study of frost formation on a horizontal cylinder under cross flow [J].
Lee, YB ;
Ro, ST .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (06) :468-474