Routine sampling and the control of Legionella spp. in cooling tower water systems

被引:47
作者
Bentham, RH [1 ]
机构
[1] Flinders Univ S Australia, Dept Environm Hlth, Adelaide, SA 5001, Australia
关键词
D O I
10.1007/s002840010133
中图分类号
Q93 [微生物学];
学科分类号
071005 ; 100705 ;
摘要
Cooling water samples from 31 cooling tower systems were cultured for Legionella over a 16-week summer period. The selected systems were known to be colonized by Legionella. Mean Legionella counts and standard deviations were calculated and rime series correlograms prepared for each system. The standard deviations of Legionella counts in all the systems were very large, indicating great variability in the systems over the time period. Time series analyses demonstrated that in the majority of cases there was no significant relationship between the Legionella counts in the cooling tower at time of collection and the culture result once it was available. In the majority of systems (25/28), culture results from Legionella samples taken from the same systems 2 weeks apart were not statistically related. The data suggest that determinations of health risks from cooling towers cannot be reliably based upon single or infrequent Legionella tests.
引用
收藏
页码:271 / 275
页数:5
相关论文
共 16 条
[1]   Legionella:: from environmental habitats to disease pathology, detection and control [J].
Atlas, RM .
ENVIRONMENTAL MICROBIOLOGY, 1999, 1 (04) :283-293
[2]  
*AUSTR STAND, 1989, A3666 AUSTR STAND
[3]   FIELD TRIAL OF BIOCIDES FOR CONTROL OF LEGIONELLA IN COOLING-TOWERS [J].
BENTHAM, RH ;
BROADBENT, CR .
CURRENT MICROBIOLOGY, 1995, 30 (03) :167-172
[4]   A MODEL FOR AUTUMN OUTBREAKS OF LEGIONNAIRES-DISEASE ASSOCIATED WITH COOLING-TOWERS, LINKED TO SYSTEM OPERATION AND SIZE [J].
BENTHAM, RH ;
BROADBENT, CR .
EPIDEMIOLOGY AND INFECTION, 1993, 111 (02) :287-295
[5]   ENVIRONMENTAL-FACTORS AFFECTING THE COLONIZATION OF COOLING-TOWERS BY LEGIONELLA SPP IN SOUTH-AUSTRALIA [J].
BENTHAM, RH .
INTERNATIONAL BIODETERIORATION & BIODEGRADATION, 1993, 31 (01) :55-63
[6]  
BHOPAL RS, 1991, J INFECTION, V22, P2378
[7]  
COLBOURNE JS, 1989, BIODETERIORATION, V7, P36
[8]  
DENNIS PJ, 1988, LAB MANUAL LEGIONELL, V4, P31
[9]  
EDELSTEIN PH, 1984, VAWMCLD841
[10]   INTRACELLULAR MULTIPLICATION OF LEGIONELLA-PNEUMOPHILA IN AMEBAS ISOLATED FROM HOSPITAL HOT WATER TANKS [J].
FIELDS, BS ;
SANDEN, GN ;
BARBAREE, JM ;
MORRILL, WE ;
WADOWSKY, RM ;
WHITE, EH ;
FEELEY, JC .
CURRENT MICROBIOLOGY, 1989, 18 (02) :131-137