Fault-current limiter applications in medium- and high-voltage power distribution systems

被引:30
作者
Wu, AY [1 ]
Yin, YX [1 ]
机构
[1] Global Engn Co, Atlanta, GA 30356 USA
关键词
fault-current limiters; minimum fault-current change rate (di/dt); trigger level;
D O I
10.1109/28.658751
中图分类号
T [工业技术];
学科分类号
08 [工学];
摘要
Electronically triggered fault-current limiters have been used in medium-and high-voltage power distribution systems to limit the available short-circuit current tu a lower level, so that the underrated switchgear can be operated safely, However, to insure a safe and proper usage of these devices, the following major operating parameters need to be considered: 1) selection of trigger level; 2) selection of di/dt; 3) effect of the capacitor bank and stray capacitances; and 4) coordination between these devices and phase overcurrent (o/c) relays at the faulted breaker, This paper will examine these major operating parameters, evaluate the performance of the current limiters tinder various simulated fault conditions, and develop application guidelines fur current limiters.