Multi-criteria analysis of combined cooling, heating and power systems in different climate zones in China

被引:157
作者
Wang Jiang-Jiang [1 ]
Zhang Chun-Fa [1 ]
Jing You-Yin [1 ]
机构
[1] N China Elect Power Univ, Sch Energy & Power Engn, Baoding 071003, Hebei, Peoples R China
关键词
Combined cooling; heating and power (CCHP) system; Multi-criteria analysis; Climate zones; Energy demand; Operation mode; China; GREENHOUSE-GAS EMISSIONS; TRIGENERATION SYSTEMS; ENERGY EFFICIENCY; OPTIMAL-DESIGN; ECONOMIC-FEASIBILITY; GENERATION SYSTEMS; PROGRAMMING-MODEL; COGENERATION; PERFORMANCE; OPTIMIZATION;
D O I
10.1016/j.apenergy.2009.06.027
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The design and operation of combined cooling, heating and power (CCHP) systems are greatly dependent upon the seasonal atmospheric conditions, which determine thermal and power demands of buildings. This paper presents a mathematical analysis of CCHP system in comparison to separate system. The corresponding primary energy consumption in thermal demand management (TDM) and electrical demand management (EDM) operation modes are deduced. Three relative criteria, primary energy saving (PES), CO2 emission reduction (CO2ER), and annual total cost saving (ATCS) are employed to evaluate the respective performances of CCHP systems for a hypothetical building in five different climate zones from the technical, environmental and economic aspects. The results indicate that CCHP system in TDM mode in the cold area, where the building requires more heating during the year, achieves more benefit over separate system while CCHP system in EDM mode suits the building having stable thermal demand in mild climate zone. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1247 / 1259
页数:13
相关论文
共 51 条
[1]   Multi-criteria evaluation of residential energy supply systems [J].
Alanne, Kari ;
Salo, Ahti ;
Saari, Arto ;
Gustafsson, Stig-Inge .
ENERGY AND BUILDINGS, 2007, 39 (12) :1218-1226
[2]  
[Anonymous], BASE LINE INVESTIGAT
[3]   A mixed integer programming model for optimal design of trigeneration in a hospital complex [J].
Arcuri, P. ;
Florio, G. ;
Fragiacomo, P. .
ENERGY, 2007, 32 (08) :1430-1447
[4]   Optimal design of CHCP plants in the civil sector by thermoeconomics [J].
Cardona, E. ;
Piacentino, A. .
APPLIED ENERGY, 2007, 84 (7-8) :729-748
[5]   A new approach to exergoeconomic analysis and design of variable demand energy systems [J].
Cardona, E ;
Piacentino, A .
ENERGY, 2006, 31 (04) :490-515
[6]   A methodology for sizing a trigeneration plant in mediterranean areas [J].
Cardona, E ;
Piacentino, A .
APPLIED THERMAL ENGINEERING, 2003, 23 (13) :1665-1680
[7]   Matching economical, energetic and environmental benefits: An analysis for hybrid CHCP-heat pump systems [J].
Cardona, Ennio ;
Piacentino, Antonio ;
Cardona, Fabio .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (20) :3530-3542
[8]   Integration of absorption cooling systems into micro gas turbine trigeneration systems using biogas: Case study of a sewage treatment plant [J].
Caries Bruno, Joan ;
Ortega-Lopez, Victor ;
Coronas, Alberto .
APPLIED ENERGY, 2009, 86 (06) :837-847
[9]   Trigeneration primary energy saving evaluation for energy planning and policy development [J].
Chicco, Gianfranco ;
Mancarella, Pierluigi .
ENERGY POLICY, 2007, 35 (12) :6132-6144
[10]   Assessment of the greenhouse gas emissions from cogeneration and trigeneration systems. Part I: Models and indicators [J].
Chicco, Gianfranco ;
Mancarella, Pierluigi .
ENERGY, 2008, 33 (03) :410-417