Improvement of first swing stability limit by utilizing full benefit of shunt FACTS devices

被引:105
作者
Haque, MH [1 ]
机构
[1] Nanyang Technol Univ, Sch Elect & Elect Engn, Ctr Adv Power Elect, Singapore 639798, Singapore
关键词
dynamic analysis; equal area criterion (EAC); flexible ac transmission system (FACTS); first swing stability; static synchronous compensator (STATCOM); static var compensator (SVC);
D O I
10.1109/TPWRS.2004.836243
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a new control strategy of shunt flexible ac transmission system (FACTS) devices to improve the first swing stability limit of a simple power system. It is shown that the speed based bang-bang control (BBC) is unable to use the entire decelerating area in maintaining stability. The proposed control strategy improves the stability limit first by maximizing the decelerating area and then fully utilizing it in counterbalancing the accelerating area. This requires to continue the operation of shunt FACTS devices at full capacitive rating until the machine speed reaches a reasonable negative value during the first return journey. Afterwards, the control can be switched to continuous type to improve system damping in subsequent swings. The proposed control strategy is then applied to both static var compensator and static synchronous compensators placed in a single machine infinite bus system. The same control strategy is also used for some faults in a multimachine system. In both the systems, it is found that the proposed control can provide significantly higher stability limit than that of the BBC. The mechanism of improving the stability limit is also described.
引用
收藏
页码:1894 / 1902
页数:9
相关论文
共 12 条
[1]   POWER OSCILLATION DAMPING USING CONTROLLED REACTIVE POWER COMPENSATION - A COMPARISON BETWEEN SERIES AND SHUNT APPROACHES [J].
ANGQUIST, L ;
LUNDIN, B ;
SAMUELSSON, J .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (02) :687-700
[2]  
Byerly R., 1974, STABILITY LARGE ELEC
[4]   DETERMINATION OF 1ST SWING STABILITY LIMIT OF MULTIMACHINE POWER-SYSTEMS THROUGH TAYLOR-SERIES EXPANSIONS [J].
HAQUE, MH ;
RAHIM, AHMA .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1989, 136 (06) :373-379
[5]  
Hingorani N. G., 1999, Understanding FACTS: Concepts and technology of flexible AC Transmission systems
[6]  
KUMKRATUG P, 2003, P I ELECT ENG GEN TR, V150, P155
[7]   ADVANCED SVC CONTROL FOR DAMPING-POWER SYSTEM OSCILLATIONS [J].
LERCH, E ;
POVH, D ;
XU, L .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (02) :524-535
[8]  
MUSAVI MT, 1985, IEEE T CIRCUITS SYST, V32, P712, DOI 10.1109/TCS.1985.1085778
[9]   A robust control strategy for shunt and series reactive compensators to damp electromechanical oscillations [J].
Noroozian, M ;
Ghandhari, M ;
Andersson, G ;
Gronquist, J ;
Hiskens, I .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) :812-817
[10]   DAMPING TORQUE ANALYSIS OF STATIC VAR SYSTEM CONTROLLERS [J].
PADIYAR, KR ;
VARMA, RK .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (02) :458-465