A practical method for assessing the effectiveness of vector surge relays for distributed generation applications

被引:101
作者
Freitas, W [1 ]
Huang, ZY
Xu, WS
机构
[1] Univ Alberta, Dept Elect & Comp Engn, Edmonton, AB T6G 2V4, Canada
[2] Pacific NW Natl Lab, Energy Sci & Technol Div, Richland, WA 99352 USA
关键词
distributed generation; islanding detection; synchronous generators; vector shift relays; vector surge relays;
D O I
10.1109/TPWRD.2004.838637
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 [电气工程]; 0809 [电子科学与技术];
摘要
This paper presents a simple and reliable method for predicting the islanding detection performance. of vector surge relays. The relay performance is characterized by A tripping-time versus power-imbalance curve. With the curve, one can determine the time taken by a vector surge relay to detect islanding for any generation-load mismatch level. The main contribution of this paper is the development of analytical formulas for-directly determining the behavior of vector surge relays. As a result, efforts needed to asses the relay performance for a given distributed generation scheme can be simplified significantly. The accuracy of the formulas has been verified by extensive simulation study results.
引用
收藏
页码:57 / 63
页数:7
相关论文
共 5 条
[1]
[Anonymous], 3723 CIGRE WORK GROU
[2]
*CIRED, 1999, 4 CIRED WORK GROUP
[3]
*IEEE, 1988, IEEE GUID INT DISP S
[4]
Jenkins N, 2000, EMBEDDED GENERATION
[5]
Kundur P., 1994, POWER SYSTEM STABILI