Sensitivity analysis of a maritime located night ventilated library building

被引:37
作者
Finn, Donal P. [1 ]
Connolly, Darragh
Kenny, Paul
机构
[1] Univ Coll Dublin, Sch Elect Elect & Mech Engn, Dublin 4, Ireland
[2] Univ Coll Dublin, Urban Inst, Dublin 4, Ireland
[3] Univ Coll Dublin, Sch Architecture, Dublin 4, Ireland
关键词
night ventilation; building sensitivity analysis; maritime climate;
D O I
10.1016/j.solener.2006.10.008
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
An examination of the role of design and operational parameters in a night ventilated library building located in Ireland, and which is Subject to a maritime type climate, is considered. For this investigation, a self-contained space within the library building is analysed. A dynamic model of the space is created using the ESPr simulation package, which is compared with building data obtained from an experimental monitoring programme. Calculation of the mean bias deviation between the predicted and experimental data indicates agreement better than 0.45 degrees C for the dry bulb temperature and 1. 1 degrees C for the mean radiant temperature. Using ESPr predictions, the role of different building design and operational parameters are examined by means of parametric analysis including building mass, ventilation duration, internal gain and ventilation rates. Compared to a reference base of the existing building, increasing the building mass was found to achieve a significant reduction in internal dry resultant temperatures, with a decrease of between 2 and 3 degrees C observed when mass was increased from 800 k g/m(2) to 1600 kg/m(2). Reducing building internal gains from 40 W/m(2) to 20 W/m(2) was observed to have the potential of further reducing dry resultant temperatures by up to 1 degrees C. Examination of night ventilation rates indicated that increasing night ventilation up to 10 ACH was observed to have a significant affect on reduction of dry resultant temperature, but further increases of air changes were observed to have a negligible effect. (c) 2006 Elsevier Ltd. All rights reserved.
引用
收藏
页码:697 / 710
页数:14
相关论文
共 17 条
[1]  
*AMCA, 1999, 500699 LAB METH TEST
[2]  
*ASHRAE, 2001, HDB FUND
[3]  
BIRTLES AB, 1996, WORLD REN EN C DENV, P259
[4]   Night ventilation for building cooling in summer [J].
Blondeau, P ;
Sperandio, M ;
Allard, F .
SOLAR ENERGY, 1997, 61 (05) :327-335
[5]   Passive cooling in a low-energy office building [J].
Breesch, H ;
Bossaer, A ;
Janssens, A .
SOLAR ENERGY, 2005, 79 (06) :682-696
[6]  
*CIBSE, 2000, GUID H CIBSE
[7]  
Fletcher J., 1996, NIGHT COOLING CONTRO
[8]   Experimental evaluation of night ventilation phenomena [J].
Geros, V ;
Santamouris, M ;
Tsangrasoulis, A ;
Guarracino, G .
ENERGY AND BUILDINGS, 1999, 29 (02) :141-154
[9]   Effectiveness of mass and night ventilation in lowering the indoor daytime temperatures. Part I: 1993 experimental periods [J].
Givoni, B .
ENERGY AND BUILDINGS, 1998, 28 (01) :25-32
[10]   How to use natural ventilation to cool narrow office buildings [J].
Gratia, E ;
Bruyère, I ;
De Herde, A .
BUILDING AND ENVIRONMENT, 2004, 39 (10) :1157-1170