Optimum fault current limiter placement with search space reduction technique

被引:79
作者
Teng, J. -H. [1 ]
Lu, C. -N. [2 ]
机构
[1] I Shou Univ, Dept Elect Engn, Dashu Township 840, Kaohsiung Cty, Taiwan
[2] Natl Sun Yat Sen Univ, Dept Elect Engn, Kaohsiung, Taiwan
关键词
SYSTEMS; VOLTAGE; FCL;
D O I
10.1049/iet-gtd.2009.0340
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
080906 [电磁信息功能材料与结构]; 082806 [农业信息与电气工程];
摘要
A fault occurring in power networks normally results in a large short-circuit current flow in the system, which may exceed the rating of existing circuit breakers and can damage system equipments. Because of difficulty in power network reinforcement and the interconnection of more distributed generations, fault current level has become a serious problem in transmission and distribution system operations. The utilisation of fault current limiters (FCLs) in power systems could provide an effective way to suppress fault currents. In a loop transmission or distribution system, the advantages would greatly depend on the number and locations of FCL installations. The authors propose a method to determine the optimum number and locations for FCL placement in terms of installing smallest FCLs circuit parameters to restrain short-circuit currents under circuit breakers' interrupting ratings. In the proposed approach, the sensitivity factor, defined as the reduction of bus fault currents because of a given variation in the branch parameter, is derived and used to choose better candidates for active FCL installations. The search space for FCL installations can be reduced by using the proposed sensitivity factor calculation; therefore the computational efficiency and accuracy can be improved. A genetic-algorithm-based method is then designed to include the sensitivity information in searching for the best locations and parameters of FCLs. The test results demonstrate the efficiency and accuracy of the proposed method.
引用
收藏
页码:485 / 494
页数:10
相关论文
共 23 条
[1]
[Anonymous], 1984, Power Generation Operation and Control
[2]
*CIGR, 2003, 239 CIGR
[3]
DUGGAN P, 2006, IEEE POWER ENG SOC G, V2, P1423
[4]
Duggan PM, 2008, IEEE POW ENER SOC GE, P2636
[5]
Restoration of directional overcurrent relay coordination in distributed generation systems utilizing fault current limiter [J].
El-Khattam, Walid ;
Sidhu, Tarlochan S. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (02) :576-585
[6]
*EPRI, 2008, 1016389 EPRI
[7]
Goldberg DE., 1989, GENETIC ALGORITHMS S, V13
[8]
Grainger J. J., 1994, Power System Analysis
[9]
Optimal location assignment and design of superconducting fault current limiters applied to loop power systems [J].
Hongesombut, K ;
Mitani, Y ;
Tsuji, K .
IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2003, 13 (02) :1828-1831
[10]
Hongesombut K., 2003, Transactions of the Institute of Electrical Engineers of Japan, Part B, V123-B, P1054, DOI 10.1541/ieejpes.123.1054