Synchronized phasor data based energy function analysis of dominant power transfer paths in large power systems

被引:67
作者
Chow, Joe H. [1 ]
Chakrabortty, Aranya
Arcak, Murat
Bhargava, Bharat
Salazar, Armando
机构
[1] Rensselaer Polytech Inst, Dept Elect & Comp Syst Engn, Troy, NY 12180 USA
[2] So Calif Edison Co, Rosemead, CA 91770 USA
基金
美国国家科学基金会;
关键词
energy function; power system stability; power transfer path; synchronized phasor measurement unit (PMU);
D O I
10.1109/TPWRS.2007.895162
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Many large interconnected power systems such as the U.S. eastern interconnection and the U.S. western power system are characterized by many power transfer paths or interfaces with high loading. Disruptions of these transfer paths frequently lead to increased loading on neighboring transfer paths, which themselves will become less secure and could cause further disruptions. State estimators have limited performance under large system disruptions, because of low sampling rates and potentially poor solution quality due to topology errors. Furthermore, disruptions in external power systems cannot be readily seen by control room operators because most state estimators only use reduced models for external systems. A system of well-placed phasor measurement units (PMUs) that provide voltage and current magnitude and phase at a high sampling rate can provide useful system dynamic security information. In this paper we apply energy function analysis using phasor data to monitor the dynamic status of power transfer paths. The ideas will be illustrated using actual data captured by several PMUs in the U.S. western power system.
引用
收藏
页码:727 / 734
页数:8
相关论文
共 19 条
[1]  
BERGEN A, 1999, POWER SYSTME ANAL
[2]  
Centeno V., 1993, IEEE Computer Applications in Power, V6, P12, DOI 10.1109/67.238199
[3]   THE CLOSEST UNSTABLE EQUILIBRIUM POINT METHOD FOR POWER-SYSTEM DYNAMIC SECURITY ASSESSMENT [J].
CHIANG, HD ;
THORP, JS .
IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS, 1989, 36 (09) :1187-1200
[4]  
Chow J. H., 1982, TIME SCALE MODELING
[5]  
FOUAD A, 1996, POWER SYSTEM TRANSIE
[6]   Keeping an eye on power system dynamics [J].
Hauer, J ;
Trudnowski, D ;
Rogers, G ;
Mittelstadt, B ;
Litzenberger, W ;
Johnson, J .
IEEE COMPUTER APPLICATIONS IN POWER, 1997, 10 (04) :50-54
[7]   APPLICATION OF PRONY ANALYSIS TO THE DETERMINATION OF MODAL CONTENT AND EQUIVALENT MODELS FOR MEASURED POWER-SYSTEM RESPONSE [J].
HAUER, JF .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (03) :1062-1068
[8]  
Hingorani Narain G., 2000, UNDERSTANDING FACTS
[9]   ADAPTIVE TRANSMISSION-SYSTEM RELAYING [J].
HOROWITZ, SH ;
PHADKE, AG ;
THORP, JS .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1436-1445
[10]   Feasibility study of using synchronized phasor measurements for generator dropping controls in the Colstrip system [J].
Kosterev, DN ;
Esztergalyos, J ;
Stigers, CA .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1998, 13 (03) :755-761