Thailand ventilation comfort chart

被引:89
作者
Khedari, J [1 ]
Yamtraipat, N [1 ]
Pratintong, N [1 ]
Hirunlabh, J [1 ]
机构
[1] King Mongkuts Univ Technol Thonburi, Sch Energy & Mat, Energy Technol Div, Bangkok, Thailand
关键词
thermal comfort; air velocity; relative humidity; temperature; classroom building;
D O I
10.1016/S0378-7788(00)00050-5
中图分类号
TU [建筑科学];
学科分类号
0813 [建筑学];
摘要
The paper presents a ventilation comfort chart that has been developed under Thailand climate and using Thai volunteers. 183 male and 105 female college-age subjects were exposed to different thermal conditions in order to investigate the effect of air velocity on thermal comfort in ventilated "non-conditioned" spaces. To this end, commercial electric fans were used to control the air velocity near the subjects. The air velocity varied between 0.2 and 3 m/s. Room conditions varied between 26 degrees C and 36 degrees C (D.B.T.) and 50-80% relative humidity. Thermal sensation vote was recorded through a questionnaire. The Predicted Mean Vote was used to determine the indoor neutral temperature. This developed chart could be used to design ventilation system for offices and classrooms. (C) 2000 Elsevier Science S.A. All rights reserved.
引用
收藏
页码:245 / 249
页数:5
相关论文
共 15 条
[1]
[Anonymous], THERM ENV COND HUM O
[2]
[Anonymous], ASHRAE J AUG
[3]
ARENS, 1980, P AM SECT INT SOL EN, P1202
[4]
ARENS, 1983, ASHRAE T, V89, P245
[5]
ASHRAE, 1993, ASHRAE HDB 1993 FUND
[6]
BUSCH JF, 1990, ASHRAE TRAN, V96, P859
[7]
Fanger P.O., 1972, Thermal Comfort Analysis and Application in Environmental Engineering, P244, DOI DOI 10.1016/S0038-092X(00)00100-6
[8]
IFTIKHAR A, 1996, REV CLIMATIC CONDITI, P1350
[9]
JITKHAJORNWANIC.K, 1995, ASHRAE T S, P1181
[10]
Thermal comfort and building design in the tropical climates [J].
Mallick, FH .
ENERGY AND BUILDINGS, 1996, 23 (03) :161-167