An adaptive control for UPS to compensate unbalance and harmonic distortion using a combined capacitor/load current sensing

被引:117
作者
Escobar, G. [1 ]
Mattavelli, P.
Stankovic, A. M.
Valdez, Andres A.
Leyva-Ramos, Jesus
机构
[1] Res Inst Sci & Technol San Luis Potosi, IPICYT, Div Appl Math, San Luis Potosi 78216, Mexico
[2] Univ Udine, Dept Elect Mech & Management Engn, DIEGM, I-33100 Udine, Italy
[3] Northeastern Univ, Dept Elect & Comp Engn, Boston, MA 02115 USA
关键词
adaptive control; nonlinear systems; uninterruptible power supply (UPS) systems;
D O I
10.1109/TIE.2007.891998
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper investigates the control of an uninterruptible power supply (UPS) using a combined measurement of capacitor and load currents in the same current sensor arrangement. The purpose of this combined measurement is, on one hand, to reach a similar performance as that obtained in the inductor current controller with load current feedforward and, on the other hand, to easily obtain an estimate of the inductor current for overcurrent protection capability. Based on this combined current measurement, a voltage controller based on resonant harmonic filters is investigated in order to compensate for unbalance and harmonic distortion on the load. Adaptation is included to cope with uncertainties in the system parameters. It is shown that after transformations the proposed controller gets a simple and practical form that includes a bank of resonant filters, which is in agreement with the internal model principle and corresponds to similar approaches proposed recently. The controller is based on a frequency-domain description of the periodic disturbances, which include both symmetric components, namely, the negative and positive sequence. Experimental results on the output stage of a three-phase three-wire UPS are presented to assess the performance of the proposed algorithm.
引用
收藏
页码:839 / 847
页数:9
相关论文
共 16 条
[1]  
Ali SM, 1998, IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS (ISIE 98) - PROCEEDINGS, VOLS 1 AND 2, P196, DOI 10.1109/ISIE.1998.707776
[2]   Analysis and design of direct power control (DPC) for a three phase synchronous rectifier via output regulation subspaces [J].
Escobar, G ;
Stankovic, AM ;
Carrasco, JM ;
Galván, E ;
Ortega, R .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2003, 18 (03) :823-830
[3]   Application of a sinusoidal internal model to current control of three-phase utility-interface converters [J].
Fukuda, S ;
Imamura, R .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2005, 52 (02) :420-426
[4]   WAVEFORM COMPENSATION OF PWM INVERTER WITH CYCLIC FLUCTUATING LOADS [J].
HANEYOSHI, T ;
KAWAMURA, A ;
HOFT, RG .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1988, 24 (04) :582-589
[5]  
JOU HL, 1994, IEEE POWER ELECTRON, P1443, DOI 10.1109/PESC.1994.373874
[6]  
JUNG SL, 1994, IEEE POWER ELECTRON, P552, DOI 10.1109/PESC.1994.349682
[7]  
Khalil H. K., 2002, NONLINEAR SYSTEMS, V3
[8]  
MANNING CD, 1994, IEE C
[10]   Dissipativity-based adaptive and robust control of UPS [J].
Mattavelli, P ;
Escobar, G ;
Stankovic, AM .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2001, 48 (02) :334-343