A near-optimal control strategy for cool storage systems with dynamic electric rates (RP-1252)

被引:44
作者
Braun, James E. [1 ]
机构
[1] Purdue Univ, W Lafayette, IN 47907 USA
来源
HVAC&R RESEARCH | 2007年 / 13卷 / 04期
关键词
D O I
10.1080/10789669.2007.10390972
中图分类号
O414.1 [热力学];
学科分类号
摘要
A near-optimal control method was developed for charging and discharging of cool storage systems when real-time pricing (RTP) electric rates are available The algorithm requires relatively low-cost measurements (cooling load and storage state of charge), requires very little plant-specific information, is computationally simple, and ensures that building cooling requirements are always met (e.g., storage isn't prematurely depleted). The control method was evaluated for ice storage systems using a simulation tool for different combinations of cooling plants, storage If sizes, buildings, locations, and RTP rates. The simplified method worked well in all cases and gave annual costs within approximately 2% of the minimum possible costs associated with optimal control.
引用
收藏
页码:557 / 580
页数:24
相关论文
共 15 条
[1]  
*ASHRAE, 2003, ASHRAE HDB HVAC APPL, pCH41
[2]  
BRAUN JE, 1992, ASHRAE TRAN, V98, P893
[3]  
BRAUN JE, 2007, ASHRAE T, V113
[4]  
Drees K. H., 1996, HVAC&R RES, V2, P312, DOI DOI 10.1080/10789669.1996.10391352
[5]  
Drees KH, 1995, HVACR Research, V1, P143, DOI 10.1080/10789669.1995.10391315
[6]  
Henze G.P., 1997, HVACR RES, V3, P233
[7]   An overview of optimal control for central cooling plants with ice thermal energy storage [J].
Henze, GP .
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2003, 125 (03) :302-309
[8]   Impact of real-time pricing rate uncertainty on the annual performance of cool storage systems [J].
Henze, GP .
ENERGY AND BUILDINGS, 2003, 35 (03) :313-325
[9]  
Henze GP, 1999, ASHRAE T, V105, P553
[10]  
*NREL, 1995, NRELSP4637668