A new critical formula and mathematical model of double-tap interphase reactor in a six-phase tap-changer diode rectifier

被引:55
作者
Pan Qijun [1 ]
Ma Weiming [1 ]
Liu Dezhi [1 ]
Zhao Zhihua [1 ]
Meng Jin [1 ]
机构
[1] USN, Res Inst Power Elect Technol, Wuhan 430033, Peoples R China
基金
中国国家自然科学基金;
关键词
critical formula; interphase reactor; mathematical model; six-phase diode rectifier; tap-changer;
D O I
10.1109/TIE.2006.888800
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 [计算机科学与技术];
摘要
This paper presents a new practical formula to calculate the critical value of interphase reactor (IPR) in a six-phase diode rectifier with tap-changer. In addition, a mathematical model of the double-tap IPR has been established by equivalent circuit method. Simulation and experimental results verify the validity of the formula and mathematical model. On the basis of the above achievements, a simple and effective approach is provided to design the IPR and to analyze the performance of the whole system.
引用
收藏
页码:479 / 485
页数:7
相关论文
共 9 条
[1]
ARRILLAGA J, 1991, P I ELECT ENG B, V138, P15
[2]
Choi S, 1997, IEEE T IND APPL, V33, P531, DOI 10.1109/28.568020
[3]
A new active interphase reactor for 12-pulse rectifiers provides clean power utility interface [J].
Choi, S ;
Enjeti, PN ;
Lee, HH ;
Pitel, IJ .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1996, 32 (06) :1304-1311
[4]
NEW METHOD FOR REDUCING HARMONICS INVOLVED IN INPUT AND OUTPUT OF RECTIFIER WITH INTERPHASE TRANSFORMER [J].
MIYAIRI, S ;
IIDA, S ;
NAKATA, K ;
MASUKAWA, S .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1986, 22 (05) :790-797
[5]
PAN Q, 2004, IEEE IECON 04, V1, P850
[6]
QIJUN P, 1999, J NAVAL U ENG, P13
[7]
QIJUN P, 2003, J NAVAL U ENG, V15, P26
[8]
QIJUN P, 1999, THESIS NAVAL U ENG W
[9]
WEIMING M, 1996, T CHINA ELECTROTECHN, V11, P36