This paper provides a self-healing strategy to deal with catastrophic events when power system vulnerability analysis indicates that the system is approaching an extreme emergency state. In our approach, the system is adaptively divided into smaller islands with consideration of quick restoration. Then, a load shedding scheme based on the rate of frequency decline is applied. The proposed scheme is tested on a 179-bus, 20-generator sample system and shows very good performance.