Influence of oil on flow condensation heat transfer of R410A inside 4.18 mm and 1.6 mm inner diameter horizontal smooth tubes

被引:78
作者
Huang, Xiangchao [1 ]
Ding, Guoliang [1 ]
Hu, Haitao [1 ]
Zhu, Yu [1 ]
Peng, Hao [1 ]
Gao, Yifeng [2 ]
Deng, Bin [3 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
[2] Int Copper Assoc Shanghai Off, Shanghai 200020, Peoples R China
[3] Golden Dragon Precise Copper Tube Grp Inc, Inst Heat Transfer Technol, Shanghai 200135, Peoples R China
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2010年 / 33卷 / 01期
关键词
Heat exchanger; Condenser; Smooth tube; Heat transfer; Parameter; Oil; PRESSURE-DROP; TRANSFER COEFFICIENTS; MIXTURE; R134A; REFRIGERANTS; R22;
D O I
10.1016/j.ijrefrig.2009.09.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
The influence of oil on condensation heat transfer of R410A inside 4.18 mm and 1.6 mm inner diameter horizontal smooth tubes is investigated experimentally. The experimental condensing temperature is 40 degrees C, and nominal oil concentration range is from 0% to 5%. The test results indicate that the presence of oil deteriorates the heat transfer, and the deterioration effect becomes obvious with the increase of oil concentration. At oil concentration of 5%, the heat transfer coefficient decreases by maximum 24.9% and 28.5% for 4.18 mm and 1.6 mm tubes, respectively. A new correlation for heat transfer coefficients of R410A-oil mixture flow condensation inside smooth tubes is proposed, which agrees with all the experimental data within a deviation of -30% similar to +20%. (c) 2009 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:158 / 169
页数:12
相关论文
共 27 条
[1]  
*ASHRAE, 1996, 4141996 ASHRAE
[2]   In-tube condensation of mixture of R134a and ester oil: empirical correlations [J].
Bassi, R ;
Bansal, PK .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2003, 26 (04) :402-409
[3]   Experimental investigation on condensation heat transfer and pressure drop of new HFC refrigerants (R134a, R125, R32, R410A, R236ea) in a horizontal smooth tube [J].
Cavallini, A ;
Censi, G ;
Del Col, D ;
Doretti, L ;
Longo, GA ;
Rossetto, L .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (01) :73-87
[4]   EFFECT OF LUBRICATING OIL CONTAMINATION ON CONDENSATION IN REFRIGERANT-R22 [J].
CAWTE, H .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1992, 16 (04) :327-340
[5]   Condensation in smooth horizontal tubes [J].
Dobson, MK ;
Chato, JC .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1998, 120 (01) :193-213
[6]  
Eckels S.J., 1998, ASHRAE T, V104, P366
[7]  
Eckels S.J, 1998, ASHRAE Transcr., V104, P376
[8]  
Eckels SJ, 1994, ASHRAE T, V100, P283
[9]  
ECKELS SJ, 1999, ASHRAE T, V105, P442
[10]  
HARALICK RM, 1994, CVGIP-IMAG UNDERSTAN, V60, P245, DOI 10.1006/cviu.1994.1055