Comparing secondary voltage regulation and shunt compensation for improving voltage stability and transfer capability in the Italian power system

被引:29
作者
Cañizares, CA
Cavallo, C
Pozzi, M
Corsi, S
机构
[1] Univ Waterloo, Dept Elect & Comp Engn, Waterloo, ON N2L 3G1, Canada
[2] CESI, I-30134 Milan, Italy
基金
加拿大自然科学与工程研究理事会;
关键词
secondary voltage control; FACTS; shunt compensation; mechanical switched capacitors; SVC; STATCOM; voltage stability; transfer capability;
D O I
10.1016/j.epsr.2004.06.005
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper concentrates on comparing the advantages and disadvantages. including costs of using secondary voltage regulation (SVR) versus using shunt-connected controllers, in particular mechanical switched capacitors (MSC), static var compensators (SVC) and static synchronous compensators (STATCOM), to improve voltage stability (VS) and the external transfer capability (TC) of the Italian power network. Basic VS and TC concepts and tools. as well as the models of the various controllers, particularly SVR. used to obtain the results presented are described in detail. The model of the Italian system used and the assumptions made for these studies are also discussed The paper demonstrates that SVR is an option that should be seriously considered in practice when trying to improve VS and TC of power systems. (C) 2004 Elsevier B.V. All rights reserved.
引用
收藏
页码:67 / 76
页数:10
相关论文
共 15 条
[1]  
Berizzi A, 1996, IEEE T POWER SYST, V11, P1451, DOI 10.1109/59.535686
[2]   PRESENT PRACTICES AND TRENDS ON THE FRENCH POWER-SYSTEM TO PREVENT VOLTAGE COLLAPSE [J].
BOURGIN, F ;
TESTUD, G ;
HEILBRONN, B ;
VERSEILLE, J .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1993, 8 (03) :778-788
[3]   STATCOM modeling for voltage and angle stability studies [J].
Cañizares, CA ;
Pozzi, M ;
Corsi, S ;
Uzunovic, E .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2003, 25 (06) :431-441
[4]   CONDITIONS FOR SADDLE-NODE BIFURCATIONS IN AC/DC POWER-SYSTEMS [J].
CANIZARES, CA .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1995, 17 (01) :61-68
[5]   Analysis of SVC and TCSC Controllers in voltage collapse [J].
Cañizares, CA ;
Faur, ZT .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1999, 14 (01) :158-165
[6]  
CANIZARES CA, 2000, UWPFLOW CONTINUATION
[7]  
CORSI S, 1995, IEEE T POWER SYST, V10, P686, DOI 10.1109/59.387904
[8]  
CORSI S, 2000, P 2000 IEEE PES SUMM
[9]   Available transfer capability calculations [J].
Ejebe, GC ;
Tong, J ;
Waight, JG ;
Frame, JG ;
Wang, X ;
Tinney, WF .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1998, 13 (04) :1521-1527
[10]  
*EPRI, 1997, EXT TRANS MIDT STAB