Conic programming approach for static voltage stability analysis in radial networks

被引:17
作者
Jabr, R. A.
Pal, B. C.
机构
[1] Univ Notre Dame, Elect Comp & Commun Engn Dept, Zouk Mikhael, Zouk Mosbeh, Lebanon
[2] Univ London Imperial Coll Sci Technol & Med, Dept Elect & Elect Engn, London SW7 2BT, England
关键词
D O I
10.1049/iet-gtd:20060371
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
That the problem of computing the capacity limit of a radial distribution system can be formulated as a second-order cone program is shown. The implications of the conic programming formulation are 2-fold. First, the load capability of the radial system can be obtained using existing efficient implementations of polynomial time interior-point algorithms, thus avoiding the need for running a sequence of load flow solutions. Secondly, the conic objective function yields a voltage stability indicator (SI). This indicator quantifies the maximum percentage by which the current load profile can be uniformly increased before voltage collapse occurs. The proposed method is validated by computing the load capability and voltage SIs of 11 different distribution systems. Comparisons are carried out with five previously published voltage SIs.
引用
收藏
页码:203 / 208
页数:6
相关论文
共 25 条
[1]   THE CONTINUATION POWER FLOW - A TOOL FOR STEADY-STATE VOLTAGE STABILITY ANALYSIS [J].
AJJARAPU, V ;
CHRISTY, C .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (01) :416-423
[2]  
Andersen E. D., 2000, On implementing a primal-dual interiorpoint method for conic quadratic optimization
[3]   Brain Imaging - An introduction to a new approach to studying media processes and effects [J].
Anderson, DR ;
Bryant, J ;
Murray, JP ;
Rich, M ;
Rivkin, MJ ;
Zillmann, D .
MEDIA PSYCHOLOGY, 2006, 8 (01) :1-6
[4]   SHUNT CAPACITOR SIZING FOR RADIAL-DISTRIBUTION FEEDERS WITH DISTORTED SUBSTATION VOLTAGES [J].
BAGHZOUZ, Y ;
ERTEM, S .
IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) :650-657
[5]   NETWORK RECONFIGURATION IN DISTRIBUTION-SYSTEMS FOR LOSS REDUCTION AND LOAD BALANCING [J].
BARAN, ME ;
WU, FF .
IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (02) :1401-1407
[6]  
Canizares CA, 1996, IEEE T POWER SYST, V11, P1441, DOI 10.1109/59.535685
[7]   Voltage stability analysis of radial distribution networks [J].
Chakravorty, M ;
Das, D .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2001, 23 (02) :129-135
[8]   VOLTAGE COLLAPSE PROXIMITY INDICATOR - BEHAVIOR AND IMPLICATIONS [J].
CHEBBO, AM ;
IRVING, MR ;
STERLING, MJH .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1992, 139 (03) :241-252
[9]   Capacitor placement in distribution systems using heuristic search strategies [J].
Chis, M ;
Salama, MMA ;
Jayaram, S .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1997, 144 (03) :225-230
[10]   Simple and efficient method for load flow solution of radial distribution networks [J].
Das, D ;
Kothari, DP ;
Kalam, A .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1995, 17 (05) :335-346