Stabilising system frequency using HVDC between the Continental European, Nordic, and Great Britain systems

被引:32
作者
de Haan, Jerom E. S. [1 ]
Concha, Carolina Escudero [2 ]
Gibescu, Madeleine [1 ]
van Putten, Jan [3 ]
Doorman, Gerard L. [4 ]
Kling, Wil L. [1 ]
机构
[1] Eindhoven Univ Technol, Postbus 513, NL-5600 MB Eindhoven, Netherlands
[2] Royal Inst Technol KTH, Brinelvagen 68, S-10044 Stockholm, Sweden
[3] TenneT TSO BV, Utrechtseweg 310,Postbus 718, NL-6800 AS Arnhem, Netherlands
[4] Norwegian Univ Sci & Technol NTNU, OS Bragstads Pl 2e, N-7034 Trondheim, Norway
关键词
Frequency sensitivity; Power system balancing; Primary control Virtual inertia;
D O I
10.1016/j.segan.2015.12.003
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
080707 [能源环境工程]; 082001 [油气井工程];
摘要
For future efficiency improvement of the frequency containment process (primary control) within European power systems, cooperation between (multiple) synchronous areas using their controllable HVDC interconnections is optioned. However, the differences in system size, HVDC interconnection capacity, and the balancing performance per individual system will have its specific system frequency effect for each different balancing cooperation concept. Consequently, without alignment on cooperation, HVDC balancing might lead to disproportional support between systems, to frequency oscillations, reserve unreliability and non-compliancy, and to network constraints. Therefore, this work assesses frequency quality and associated DC power flows for several balancing arrangements, using a developed load-frequency control model with frequency interdependency for coupled power system. For a trilateral balancing cooperation case study, it is found that certain cooperation concepts result in undesired frequency oscillation and poor frequency quality. However, cooperation where especially fast-response services are shared, such as virtual inertia, show improved system frequency performance. For the case where power imbalances are proportionately distributed among the systems, it is concluded that power transfers over HVDC interconnections are limited and additional control optimisation can be performed. Those concepts with aligned central or coordinated control show best results for a future cooperation for balancing between synchronous areas. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:125 / 134
页数:10
相关论文
共 29 条
[1]
[Anonymous], 2011, THESIS KATHOLIEKE U
[2]
[Anonymous], 2010, P 45 INT U POWER ENG
[3]
[Anonymous], 2011, Older Australians and the internet: bridging the digital divide, P1
[4]
[Anonymous], Statistical Database
[5]
Bakken B., 1997, THESIS NORWEGIAN U T
[6]
Davies M., 2006, The 8th IEE International Conference on AC and DC Power Transmission (ACDC 2006), P30, DOI 10.1049/cp:20060007
[7]
De Haan J.E.S., 2015, ELECT POWER SYSTEM R
[8]
The economic impacts of a submarine HVDC interconnection between Norway and Great Britain [J].
Doorman, Gerard L. ;
Froystad, Dag Martin .
ENERGY POLICY, 2013, 60 :334-344
[9]
ENTSO-E, 2009, P1 POL 1 LOAD FREQ C, P1
[10]
ENTSO-E, 2014, ENTSO E DRAFT NETW C, P1