Comparison of thermal-hydraulic network control strategies

被引:5
作者
Franco, W [1 ]
Sen, M [1 ]
Yang, KT [1 ]
McClain, RL [1 ]
机构
[1] Univ Notre Dame, Dept Aerosp & Mech Engn, Hydron Lab, Notre Dame, IN 46556 USA
关键词
piping network; thermal control; control strategies;
D O I
10.1243/095965103321196677
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
A dynamic thermal-hydraulic analysis of strategies used for the control of hydronic piping and heat exchanger networks is carried out. Three common temperature control methods are analysed and compared using a mathematical model. For this purpose a general thermal network with a primary loop, a secondary loop and a bypass that has the three control systems as special cases is proposed. The primary loop includes a chiller, while the secondary has a water-air cooling coil which serves as a thermal load. Integral controllers are used to vary the valve settings to control the air temperature leaving the cooling coil. The system responses for each of the three control schemes as a function of the thermal load are then compared to assess their relative merits using the temperature drop in the chiller as a criterion.
引用
收藏
页码:35 / 47
页数:13
相关论文
共 14 条
[1]   Numerical simulation of the thermal control of heat exchangers [J].
Alotaibi, S ;
Sen, M ;
Goodwine, B ;
Yang, KT .
NUMERICAL HEAT TRANSFER PART A-APPLICATIONS, 2002, 41 (03) :229-244
[2]  
Avery G, 1998, ASHRAE J, V40, P42
[3]  
DORINI DK, 1994, Patent No. 5318106
[4]  
Fiorino DP, 1999, ASHRAE J, V41, P24
[5]   SIMPLE AND EXPLICIT FORMULAS FOR THE FRICTION FACTOR IN TURBULENT PIPE-FLOW [J].
HAALAND, SE .
JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME, 1983, 105 (01) :89-90
[6]  
HODGE BK, 1990, ANAL DESIGN ENERGY S
[7]  
Incropera F.P., 1990, FUNDAMENTALS HEAT MA
[8]  
KIRSNER PE, 1996, HEATING PIPING AIR C, V68, P73
[9]  
KIRSNER PE, 1995, HEATING PIPING AIR C, V67, P51
[10]  
KRIST GD, 1996, Patent No. 5586449