Pressure drop in downward flow of condensing steam over a horizontal bundle of square pitched tubes

被引:4
作者
Burnside, BM [1 ]
Cuthbertson, GC [1 ]
McNeil, DA [1 ]
机构
[1] Heriot Watt Univ, Dept Mech & Chem Engn, Edinburgh EH14 4AS, Midlothian, Scotland
关键词
D O I
10.1080/08916150050175453
中图分类号
O414.1 [热力学];
学科分类号
摘要
Pressure drop measurements in a 15-row steam condenser configured with in-line tubes, p/D (5) 1.33, are described. Pressures from 50 to 100 mb and Re-max in the range 1,000-18, 000 were imposed. It is shown that pressure loss coefficients for the bundle and for two-row pairs were lower than predictions for equivalent single-phase tests except near the bottom of the bundle. There was some evidence that increase in suction parameter increased this effect in the top rows. Taken together with previous investigations [3, 4], a falling trend of suction effect is evident the more closely packed the tubes are. The discrepancy between these findings and the results of simulation experiments [7] is noted.
引用
收藏
页码:259 / 273
页数:15
相关论文
共 16 条
[1]  
Al-Sanea S., 1983, Steam Condenser, P70
[2]  
Bergelin O.P., 1952, Trans. ASME, P953
[3]  
CUTHBERTSON G, 1999, THESIS HERIOTWATT U
[4]  
CUTHBERTSON G, 1999, P 6 UK NAT HEAT TRAN, P293
[5]  
Diehl J.E, 1957, PETROL REFINER, V36, P147
[6]  
DIEHL JE, 1958, 58HT20 ASME
[7]  
*ESDU, 1974, PRESS LOSS CROSSF FL
[8]  
FISHENDEN M, 1950, INTRO HEAT TRANSFER, P132
[9]   HEAT-TRANSFER AND FLOW RESISTANCE IN CONDENSATION OF LOW-PRESSURE STEAM FLOWING THROUGH TUBE BANKS [J].
FUJII, T ;
UEHARA, H ;
HIRATA, K ;
ODA, K .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1972, 15 (02) :247-&
[10]  
Fujii T., 1979, CONDENSATION HEAT TR, P35