Associations between indoor CO2 concentrations and sick building syndrome symptoms in US office buildings:: An analysis of the 1994-1996 BASE study data

被引:236
作者
Apte, MG [1 ]
Fisk, WJ [1 ]
Daisey, JM [1 ]
机构
[1] Lawrence Berkeley Lab, Indoor Environm Dept, Berkeley, CA 94720 USA
来源
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE | 2000年 / 10卷 / 04期
关键词
carbon dioxide; dose-response; sick building syndrome; multivariate logistic regression; office workers; ventilation;
D O I
10.1034/j.1600-0668.2000.010004246.x
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Higher indoor concentrations of air pollutants due, in part, to lower ventilation rates are a potential cause of sick building syndrome (SBS) symptoms in office workers. The indoor carbon dioxide (CO2) concentration is an approximate surrogate for indoor concentrations of other occupant-generated pollutants and for ventilation rate per occupant. Using multivariate logistic regression (MLR) analyses, we evaluated the relationship between indoor CO2 concentrations and SBS symptoms in occupants from a probability sample of 41 U.S. office buildings. Two CO2 metrics were constructed: average workday indoor minus average outdoor CO2 (dCO(2), range 6-418 ppm), and maximum indoor 1-h moving average CO2 minus outdoor CO2 concentrations (dCO(2)MAX). MLR analyses quantified dCO(2)/SBS symptom associations, adjusting for personal and environmental factors. A dose-response relationship (p<0.05) with odds ratios per 100 ppm dCO(2) ranging from 1.2 to 1.5 for sore throat, nose/sinus, tight chest, and wheezing was observed. The dCO(2)MAX/SBS regression results were similar.
引用
收藏
页码:246 / 257
页数:12
相关论文
共 26 条
[1]  
ACGIH, 1991, DOC THRESH LIM VAL B
[2]  
[Anonymous], 2001, EPIDEMIOLOGY BIOSTAT
[3]  
[Anonymous], 1993, INDOOR AIR, DOI DOI 10.1111/J.1600-0668.1993.00005.X
[4]  
APTE MG, 1999, P IND AIR 99 8 INT C, V1, P117
[5]  
ASHRAE, 1999, Standard 62-1999: Ventilation for acceptable indoor air quality
[6]   European indoor air quality audit project in 56 office buildings [J].
Bluyssen, PM ;
Fernandes, ED ;
Groes, L ;
Clausen, G ;
Fanger, PO ;
Valbjorn, O ;
Bernhard, CA ;
Roulet, CA .
INDOOR AIR-INTERNATIONAL JOURNAL OF INDOOR AIR QUALITY AND CLIMATE, 1996, 6 (04) :221-238
[7]  
BRIGHT DP, 1992, ALTR19920016
[8]  
BRIGHTMAN HS, 1996, P IND AIR 96 7 INT C, V3, P1033
[9]  
BRIGHTMAN HS, 1999, P IND AIR 99 LOND CO, V1, P847
[10]  
GIRMAN JR, 1995, P HLTH BUILD 95 MIL, V3, P1311