A general control algorithm for cooling towers in cooling plants with electric and/or gas-driven chillers

被引:11
作者
Braun, James E. [1 ]
机构
[1] Purdue Univ, Ray W Herrick Labs, W Lafayette, IN 47907 USA
来源
HVAC&R RESEARCH | 2007年 / 13卷 / 04期
关键词
Algorithms - Condenser tubes - Control systems - Natural gas - Operating costs;
D O I
10.1080/10789669.2007.10390973
中图分类号
O414.1 [热力学];
学科分类号
摘要
A hybrid chiller plant employs a combination of chillers that are "powered" by electricity and natural gas. This paper presents an algorithm for determining cooling tower fan settings in hybrid plants in response to loadings on individual chillers. Parameters of the algorithm are evaluated using design information for the chillers and cooling tower fans. In addition to reducing operating costs, use of the open-loop control strategy simplifies the control and improves the stability of the tower control compared with the use of a constant condenser water supply or approach to wet-bulb. Simulated plant cooling costs associated with the algorithm were compared with costs for optimized settings and were within 1% of the minimum costs. The control method is general, in the sense that it also applies to cooling plants that have all electric or all natural gas chillers.
引用
收藏
页码:581 / 598
页数:18
相关论文
共 12 条
[1]  
*ASHRAE, 2003, 2003 ASHRAE HDB HVAC, pCH41
[2]  
Braun J., 1989, ASHRAE Transactions, V95, P663
[3]  
Braun J, 2006, ASHRAE Reserach Project RP-1200 final report
[4]  
Braun J. E., 1989, ASHRAE Transactions, V95, P164
[5]  
BRAUN JE, 1990, ASHRAE TRAN, V96, P806
[6]  
Braun JE, 1988, THESIS U WISCONSIN M
[7]  
Hackner R, 1985, BUILD ENG, V91, P781
[8]  
KLEIN SA, 1988, ASHRAE T, V94, P627
[9]  
Koeppel E. A., 1995, HVACR Research, V1, P325, DOI 10.1080/10789669.1995.10391328
[10]  
LAU AS, 1985, ASHRAE T, V91, P766