Parallel operation of three-phase UPS inverters by wireless load sharing control

被引:28
作者
Byun, YB [1 ]
Koo, TG [1 ]
Joe, KY [1 ]
Kim, ES [1 ]
Seo, JI [1 ]
Kim, DH [1 ]
机构
[1] Korea Electrotechnol Res Inst, Chang Won 641120, Kyungnam, South Korea
来源
INTELEC(R): TWENTY-SECOND INTERNATIONAL TELECOMMUNICATIONS ENERGY CONFERENCE | 2000年
关键词
D O I
10.1109/INTLEC.2000.884299
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A load sharing control based on the frequency and voltage droop concept for parallel operation of two three-phase Uninterruptible Power Supply (UPS) systems with no control interconnection lines is presented in this paper. First of all, due to the use of active power and reactive power as control variables, the characteristics of output powers according to amplitude and phase differences between output voltages of two UPS systems are analyzed. Secondly, simulation results with different line impedance are demonstrated the feasibility of the wireless load sharing control. Finally, experiments are presented to verify the theoretical discussion with two three-phase 20kVA UPS systems employed TMS320C32, a kind of real time digital signal processor (DSP).
引用
收藏
页码:526 / 532
页数:7
相关论文
共 8 条
  • [1] DUAN SX, 1999, IEEE PEDS 99 JUL, P883
  • [2] Irving B. T., 2000, APEC 2000. Fifteenth Annual IEEE Applied Power Electronics Conference and Exposition (Cat. No.00CH37058), P235, DOI 10.1109/APEC.2000.826110
  • [3] OSHIMA H, 1991, INTELEC 91, P436
  • [4] RAMANOORTHY M, 1977, T I ENG INDIA, V52, P235
  • [5] SHOJINISHIKATA, 1997, T IEE JAPAN D, V117, P255
  • [6] TULADHAR A, 1998, IEEE APEC 98, V1, P321
  • [7] WU TF, 1998, IEEE PESC 98, V1, P186
  • [8] 1988, IEEE TUTORIAL COURSE, P16