Comparison of CO2 heat pump water heater performance with baseline cycle and two high COP cycles

被引:74
作者
Fernandez, Nicholas [1 ]
Hwang, Yunho [1 ]
Radermacher, Reinhard [1 ]
机构
[1] Univ Maryland, Dept Mech Engn, Ctr Environm Energy Engn, College Pk, MD 20742 USA
来源
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID | 2010年 / 33卷 / 03期
关键词
Heat pump; Air-water; Carbon dioxide; Transcritical cycle; Review; Improvement; Performance; COP; CARBON-DIOXIDE; REFRIGERANT;
D O I
10.1016/j.ijrefrig.2009.12.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
A CO2 heat pump water heater breadboard facility was built and a performance evaluation was conducted to investigate the effect of ambient temperature and hot water temperature on the overall coefficient of performance (COP) during full tank heating tests in three scenarios typical of residential water heating. Results show that the overall COP was maximized at higher ambient temperatures and at lower hot water temperatures. The overall COP was 30% higher for heating a full tank of cold water than reheating a warm tank water after standby losses. Additionally, potential COP enhancements of two cycle options were investigated. Performance enhancement of the two-stage cycle with internal heat exchanger was found only for standby loss reheating at low ambient temperatures and was 7.5%, while that of the suction line heat exchanger cycle was up to 7.9% for initial tank water heating and around 3.4% for reheating a warm tank water. (C) 2009 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:635 / 644
页数:10
相关论文
共 16 条
[1]  
*ASHRAE, 2006, 1182 ASHRAE
[2]   Carbon dioxide as refrigerant for tap water heat pumps: A comparison with the traditional solution [J].
Cecchinato, L ;
Corradi, M ;
Fornasieri, E ;
Zamboni, L .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (08) :1250-1258
[3]   Effects of refrigerant charge amount on the performance of a transcritical CO2 heat pump [J].
Cho, HY ;
Ryu, CG ;
Kim, YC ;
Kim, HY .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (08) :1266-1273
[4]  
HASHIMOTO K, 2006, IEA HEAT PUMP CTR NE, V24, P12
[5]   Theoretical evaluation of carbon dioxide refrigeration cycle [J].
Hwang, YH ;
Radermacher, R .
HVAC&R RESEARCH, 1998, 4 (03) :245-263
[6]   The performance of a transcritical CO2 cycle with an internal heat exchanger for hot water heating [J].
Kim, SG ;
Kim, YJ ;
Lee, G ;
Kim, MS .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (07) :1064-1072
[7]  
Lindberg V., 2000, UNCERTAINTIES ERRO 1
[8]   CO2-heat pump water heater:: characteristics, system design and experimental results [J].
Neksa, P ;
Rekstad, H ;
Zakeri, GR ;
Schiefloe, PA .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (03) :172-179
[9]  
*NI, 2009, LABVIEW
[10]   Residential CO2 heat pump system for combined space heating and hot water heating [J].
Stene, J .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (08) :1259-1265