HIGH-RESISTANCE FAULTS ON A MULTITERMINAL LINE - ANALYSIS, SIMULATED STUDIES AND AN ADAPTIVE DISTANCE RELAYING SCHEME

被引:23
作者
XIA, YQ [1 ]
DAVID, AK [1 ]
LI, KK [1 ]
机构
[1] HONG KONG POLYTECH,HONG KONG,HONG KONG
关键词
D O I
10.1109/61.277721
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The presence of a T-connection to a third terminal can drastically affect the performance of a distance relay at the other terminals. Fault resistance, especially high fault resistance, makes this problem more severe and complicated. Detailed analysis of the apparent impedance for these cases as seen from the relaying point is derived and, based on extensive simulations of the infeed/outfeed and fault-resistance effects on the relay characteristics, an adaptive distance relaying scheme is proposed. A microprocessor based distance relay using this new technique can quickly respond to very-high-resistance faults with maximum coverage of the protected line. The validity of this new scheme has been confirmed by real-time testing on a prototype hardware scheme.
引用
收藏
页码:492 / 498
页数:7
相关论文
共 4 条
[1]  
MIR M, 1989, IEE PUB, V302, P326
[2]   ADAPTIVE TRANSMISSION RELAYING CONCEPTS FOR IMPROVED PERFORMANCE [J].
ROCKEFELLER, GD ;
WAGNER, CL ;
LINDERS, JR ;
HICKS, KL ;
RIZY, DT .
IEEE TRANSACTIONS ON POWER DELIVERY, 1988, 3 (04) :1446-1458
[3]  
XIA YQ, 1993 IEEE PES WINT M
[4]  
1979, IEEE SPECIAL PUBLICA, V79