FAULT PROTECTION WITH A DIGITAL COMPUTER

被引:135
作者
ROCKEFELLER, GD
机构
[1] Westinghouse Electric Corporation, Newark, N.J.
来源
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS | 1969年 / PA88卷 / 04期
关键词
D O I
10.1109/TPAS.1969.292466
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A fundamental basis has been developed for the use of a time-shared stored-program digital computer to perform many of the electrical power-system protective-relay functions in a substation. Logic operations are given to detect a fault, locate it, and initiate the opening of the appropriate circuit breakers, whether the fault is in the station or on lines radiating from the station. The instantaneous values of the station voltages and currents are sampled at a 0.5-ms rate, converted to digital form, and stored for computer main-frame use. Operating times are compatible with the 25-ms breaker trip capability of modern two-cycle breakers. Computer speed in initiating tripping is a maximum of 4 ms for severe faults and a maximum of 10 ms for moderate or distant faults. Little attention has been given to hardware or programming aspects; instead this treatment represents the viewpoint of a protective-relay engineer who is attempting to answer the question: can it be done and what is involved? However, major emphasis was placed on minimizing computer main-frame duty. Copyright © 1969 by The Institute of Electrical and Electronics Engineers, Inc.