SYNCHRONIZED PHASOR MEASUREMENTS OF A POWER-SYSTEM EVENT

被引:81
作者
BURNETT, RO
MICHEL, G
BUTTS, MM
MURPHY, RJ
CEASE, TW
CENTENO, V
PHADKE, AG
机构
[1] Auburn University, Alabama Power Company, Electrical Engineering, University of Alablam
[2] BSEE from University of Arkansas, Instrument Engineer at Bellefonte Nuclear Plant
[3] Florida Power and Light's Protection and - Control Design Section, BSEE from the University of Miami and a MBA from florida International University
[4] Electrical Engineering at Virginia Tech., Microcomputer based monitoring, protection
关键词
PHASORS; SYNCHRONIZED; GPS; POWER SYSTEM; DYNAMICS; PMU; TRANSIENT DISTURBANCE; DIGITAL RECORDERS; POSITIVE SEQUENCE; STATE ESTIMATION; TRANSIENT SWINGS;
D O I
10.1109/59.336093
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The paper describes one of the first field measurements of positive sequence voltage phasors at key system buses during a recent switching operation at Plant Scherer of the Georgia Power Company. The phasor measurements were synchronized using time transmissions from the Global Positioning System (GPS) satellites. The data show the first ever observation of power swings recorded via synchronized phasors at several points on an integrated power network. Measurements were made on the Georgia Power Company (GPC) system, the Florida Power and Light (FPL) system, and on the Tennessee Valley Authority (TVA) system. The disturbance was also simulated on a stability program. Results of the simulation, and a comparison with the observed field data are also included.
引用
收藏
页码:1643 / 1649
页数:7
相关论文
共 2 条
[1]   Synchronized phasor measurements in power systems [J].
Phadke, A.G. .
IEEE Computer Applications in Power, 1993, 6 (02) :10-15
[2]  
1993, FEB PES WINT M COL O