COMPOSITE ROD INSULATORS FOR AC POWER-LINES - ELECTRICAL PERFORMANCE OF VARIOUS DESIGNS AT A COASTAL TESTING STATION

被引:26
作者
HOULGATE, RG
SWIFT, DA
机构
[1] NGD Research, CERL, CEGB
[2] Central Electricity Research Laboratories, Leatherhead, Surrey, Kelvin Avenue
关键词
D O I
10.1109/61.103691
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The electrical performance of thirty-six composite insulators - of four commercial types for each AC system level of 34.5 kV, 230 kV and 500 kV — has been determined at the CEGB Insulator Testing Station, Brighton on the south coast of England. The weathershed materials were epoxy-resin, ethylene propylene rubber and silicone rubber; half of the 230 kV insulators had no stress rings. Surface leakage current was recorded for surge levels of 25 mA, 150 mA and 500 mA; a special technique was developed to obtain the flashover statistics of the 500 kV insulators, thereby enabling performance of the composite insulator to be quantified relative to that of a string of cap and pin porcelain insulators of anti-fog design. The deterioration of the insulators was observed by making regular visual inspections. The practical consequences of the findings and the causes of the degradation are discussed. © 1990 IEEE
引用
收藏
页码:1944 / 1955
页数:12
相关论文
共 16 条
  • [1] CHERNEY EA, 1982, 2T118 CAN EL ASS POS
  • [2] CHERNEY EA, 1986, CEA7878 RES REP PROJ
  • [3] CHERNEY EA, 1982, 204 CAN EL ASS POS P
  • [4] COJAN M, 1980, CIGRE2210 PAP
  • [5] ELY CHA, 1978, CIGRE1502 PAP
  • [6] FORREST JS, 1942, J IEE, V89, P60
  • [7] HOULGATE RG, 1986, CIGRE1512 PAP
  • [8] HOULGATE RG, 1982, CIGRE3301 PAP
  • [9] HOULGATE RG, 1987, VOLTADE REST COMPOSI
  • [10] LAMBETH PJ, 1985, ACCELERATED OUTDOOR