VOLTAGE-DEPENDENT REACTIVE POWER LIMITS FOR VOLTAGE STABILITY STUDIES

被引:49
作者
LOF, PA [1 ]
ANDERSSON, G [1 ]
HILL, DJ [1 ]
机构
[1] UNIV NEWCASTLE,DEPT ELECT & COMP ENGN,NEWCASTLE,NSW 2308,AUSTRALIA
关键词
D O I
10.1109/59.373945
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents and studies a static model for synchronous generators with voltage dependent reactive power limits due to maximum stator current, maximum and minimum rotor (field) current as well as maximum rotor angle (underexcitation) limiters. The proposed generator model for static voltage stability studies can be included in an ordinary power flow program, and results from studies on a test system with twenty generators ale presented. The influence of voltage dependent reactive power limits is compared with fixed (conventional) limits, by use of the minimum singular value of the power flow Jacobian matrix and related submatrices as indicators of the static voltage stability limit.
引用
收藏
页码:220 / 228
页数:9
相关论文
共 25 条
[1]  
[Anonymous], 1992, NUMERICAL RECIPES FO
[2]  
Arrillaga J., 1983, COMPUTER MODELING EL, DOI [10.1002/9781118878286, DOI 10.1002/9781118878286]
[3]  
BORREMANS P, 1984, CIGRE3811 REP
[4]   POINT OF COLLAPSE METHODS APPLIED TO AC DC POWER-SYSTEMS [J].
CANIZARES, CA ;
ALVARADO, FL ;
DEMARCO, CL ;
DOBSON, I ;
LONG, WF ;
PAL, MK ;
SEMLYEN, A .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (02) :673-683
[5]  
CANIZARES CA, 1993, 3 P SEPOPE BELL HOR
[6]  
Elgerd O.I., 1982, ELECTRIC ENERGY SYST
[7]   VOLTAGE STABILITY EVALUATION USING MODAL-ANALYSIS [J].
GAO, B ;
MORISON, GK ;
KUNDUR, P .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1992, 7 (04) :1529-1542
[8]   PRACTICAL CONSIDERATIONS IN VOLTAGE STABILITY ASSESSMENT [J].
KUNDUR, P ;
MORISON, K ;
GAO, B .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 1993, 15 (04) :205-215
[9]  
LACHS WR, 1979, FEB IEEE POW ENG SOC
[10]  
Lawson C. J., 1974, SOLVING LEAST SQUARE