Performance analysis of a new sustainable evaporative cooling pad made from coconut coir

被引:40
作者
Rawangkul, R. [1 ]
Khedari, J. [2 ]
Hirunlabh, J. [1 ]
Zeghmati, B. [3 ]
机构
[1] King Mongkuts Univ Technol Thonburi, Sch Energy & Mat, Bldg Sci Res Ctr, Inst Sci & Technol Res & Serv Energy Technol Div, Bangkok, Thailand
[2] Kasetsart Univ, Bangkok, Thailand
[3] Univ Perpignan, Perpignan, France
关键词
sustainable engineering; agriculture waste; absorbent pad; heat and mass transfer; evaporative cooling pads;
D O I
10.1080/19397030802326726
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper reports a performance analysis for a new sustainable engineering application to beneficially reuse an abundant agricultural waste, coconut coir (Cocos nucifera), in evaporative cooling pads. Two small coconut coir pads of different configurations were fabricated and tested using a laboratory-scale experimental arrangement. The air supply velocity was controlled and varied between 1.88 and 2.79m s(-1). Heat and mass transfer coefficients, evaporative cooling efficiency and pressure drop across the two types of coconut coir pad were analysed and compared with those of a commercial rigid media paper pad. Results show that the cooling efficiency of the manufactured coconut coir evaporative cooling pad was fairly good (about 50%) and close to that of the commercial paper pad (about 47%). The average pressure drop across the two coconut coir pads was 1.5 and 5.1 Pa respectively. Correlations for heat and mass transfer coefficients expressed using Nusselt and Sherwood numbers are also reported. In addition, the cooling potential of the coconut coir pads was analysed using the average climatic conditions of the central region in Thailand throughout the year. The analysis showed that the air temperature leaving the coconut coir pad varied from 23 to 28 degrees C. Commercial development appears feasible given the coconut coir pad's good performance, lower cost and its availability throughout the country.
引用
收藏
页码:117 / 131
页数:15
相关论文
共 15 条
[1]   Evaluation of the performance of local fibers in evaporative cooling [J].
Al-Suliman, F .
ENERGY CONVERSION AND MANAGEMENT, 2002, 43 (16) :2267-2273
[2]  
[Anonymous], 2001, 1332001 ANSIASHRAE, P24
[3]  
[Anonymous], 1986, ENG AN EXP DAT, P16
[4]  
[Anonymous], 1994, 4161994 ANSIASHRAE, P28
[5]  
ASHRAE, 1983, FUND HDB
[6]  
Dowdy J. A., 1986, ASHRAE T, V92, P60
[7]  
Dowdy J. A., 1988, ASHARE T, V93, P382
[8]  
Holman J. P., 1980, THERMODYNAMICS, P770
[9]  
Holman J. P., 1992, HEAT TRANSFER, P714
[10]   Modeling and optimal design of evaporative cooling system in controlled environment greenhouse [J].
Jain, DL ;
Tiwari, GN .
ENERGY CONVERSION AND MANAGEMENT, 2002, 43 (16) :2235-2250