COLONIZATION OF FIBERGLASS INSULATION USED IN HEATING, VENTILATION AND AIR-CONDITIONING SYSTEMS

被引:30
作者
PRICE, DL
SIMMONS, RB
EZEONU, IM
CROW, SA
AHEARN, DG
机构
[1] GEORGIA STATE UNIV,DEPT BIOL,POB 4010,ATLANTA,GA 30303
[2] INTERFACE RES CORP,KENNESAW,GA 30144
来源
JOURNAL OF INDUSTRIAL MICROBIOLOGY | 1994年 / 13卷 / 03期
关键词
HVAC SYSTEMS; FUNGAL COLONIZATION; FUNGI ON FIBERGLASS;
D O I
10.1007/BF01584000
中图分类号
Q81 [生物工程学(生物技术)]; Q93 [微生物学];
学科分类号
071005 ; 0836 ; 090102 ; 100705 ;
摘要
The number of fungal species colonizing thermal and acoustic fiberglass insulations used in heating, ventilation, and air conditioning (HVAC) systems was fewer than that obtained from initial direct culture of these insulations. The colonization, determined by the microscopic observation of conidiophores with conidia, was primarily of acrylic-latex-facing material, but eventually the fungi permeated the fiberglass matrix. Isolates of Aspergillus versicolor were most often obtained from non-challenged insulation, whereas Acremonium obclavatum appeared to be the primary colonizing fungus in high-humidity (>90%) challenge chambers. At a lower humidity (about 70%) Aspergillus flavus was one of the more prominent fungi. Not all duct liner samples were equally susceptible to colonization and duct board appeared relatively resistant to colonization.
引用
收藏
页码:154 / 158
页数:5
相关论文
共 11 条
[1]   COLONIZATION BY CLADOSPORIUM-SPP OF PAINTED METAL-SURFACES ASSOCIATED WITH HEATING AND AIR-CONDITIONING SYSTEMS [J].
AHEARN, DG ;
SIMMONS, RB ;
SWITZER, KF ;
AJELLO, L ;
PIERSON, DL .
JOURNAL OF INDUSTRIAL MICROBIOLOGY, 1991, 8 (04) :277-280
[2]  
AHEARN DG, 1992, IAQ 92 ENV PEOPLE, P179
[3]  
MOREY PR, 1986, IAQ 86 MANAGING INDO, P500
[4]  
MOREY PR, 1991, IAQ 91 HLTH BUILDING, P128
[5]  
MOREY PR, 1993, IND ENV 93 C P IAQ, P128
[6]  
Pasanen P., 1993, INDOOR AIR, V3, P106
[7]   ACTIVITY OF AN INSOLUBLE ANTIMICROBIAL QUATERNARY AMINE COMPLEX IN PLASTICS [J].
PRICE, DL ;
SAWANT, AD ;
AHEARN, DG .
JOURNAL OF INDUSTRIAL MICROBIOLOGY, 1991, 8 (02) :83-90
[8]  
PRICE DL, 1993, INDOOR AIR 93 P INT, V6, P527
[9]  
PRICE DL, 1992, 1ST P ANN IAQ C EXP, P203
[10]  
WEST MK, 1989, IAQ 89 HUMAN EQUATIO, P60